1 Install and Cable the Cabinets

 

Install Off-Premises Station Wiring

Page 1-86

 

 

Figure 1-40 shows the connections for up to 24 off-premises analog telephones. Concentrations of analog line pairs are used at both buildings to minimize the off-premises wiring required. At the MDF, jumpers must be connected between 1 row/connecting block in the white field and up to 3 rows/connecting blocks in the purple field. At the station location, a WP-90929, List 1 Concentrator Cable is used. There are 8 station appearances on each of the 3 fingers of the concentrator cable.

1

6

22

5

7

7

45

3

8

9 10

5

11

 

12

 

7

7

7

7

crdf24o RPY 012398

Figure Notes

1.Locally engineered cables

2.Multi-pair protector units (primary protectors with heat coils or equivalent with sneak current protection)

3.B25A cable

4.Concentrator cable (WP90929 List 1)

5.356A adapter

6.Out-of-building wiring

7.Out-of-building analog telephones

8.Part of MDF

9.Station side (white field)

10.System side (purple field)

11.Cross-connect jumpers

12.To TN2183, TN769, TN742, or TN746B analog line circuit pack

Figure 1-40. Connections to 24 Out-of-Building Telephones

Page 94
Image 94
Lucent Technologies 555-230-128 manual Connections to 24 Out-of-Building Telephones