1Install and Cable the Cabinets
AC Power and Ground | Page |
CMC Cabinet Power Switch
! CAUTION:
The latch acts as the DC power switch and only removes DC power from the cabinet, not AC power. To remove AC power, pull the AC power cord from the appliance inlet. See Figure
1
psdmdc RPY 011998
Figure Notes
1. Latch
Figure 1-9. CMC Power Supply
Connect Cabinet Grounds and Other Grounds
The following additional grounding requirements must be met:
■The approved ground wire must be green, 6 AWG (#40) (16 mm2), copper, stranded wire (this is in addition to the ground wire in the AC power cord)