DEFINITY Enterprise Communications Server Release 6 | Issue 3 |
Installation and Test for Compact Modular Cabinets | May 1998 |
1 Install and Cable the Cabinets |
|
Install Emergency Transfer Unit and Associated Telephones | Page |
|
|
The maximum range for
(1036 m) when using 24 AWG (#5) (0.26 mm2) wire and 2200 feet (670 m) when using 26 AWG (#4) (0.14 mm2) wire. The range can extend to 5000 feet (1524 m) using 24 AWG (#5) (0.26 mm2) wire or 4000 feet (1219 m) using 26 AWG (#4)
(0.14 mm2) wire with the use of a data link protector. The protector is an isolating transformer used to remove phantom power on the system side and
When a protector is used, the voice terminal must be locally powered by an external power supply or through the AC power cord provided with some of the
Refer to Table
Install Emergency Transfer Unit and
Associated Telephones
NOTE:
Install only 1 emergency transfer power panel per system.
Emergency transfer capability is provided by an 808A Emergency Transfer Panel (or equivalent) mounted next to the trunk/auxiliary field. See Figure
Use analog telephones for emergency transfer. The
The transfer panel provides emergency trunk bypass or
At the MDF, the unit is controlled by a connection to a yellow terminal row/connecting block in the trunk/auxiliary field. The unit is controlled by
Install the Emergency Transfer Panel
The 808A Emergency Transfer Panel is used in the following installation example.
1.Install the transfer panel on any mounting frame in either a vertical or horizontal position. The housing has ears for