259 www.national.com
CP3BT26
Figure 125. ACB Signals (SDA and SCL) TimingFigure 126. ACB Start and Stop Condition TimingFigure 127. ACB Start Condition Timing
SCL
0.7VCC
Note: In the timing tables the parameter name is added with an "o" for output signal timing and "i" for input signal timing.
0.3VCC
tSCLf
0.7VCC
0.3VCC
tSCLr
SDA
0.7VCC
0.3VCC
tSDAf
0.7VCC
0.3VCC
tSDAr
DS106
SCL
SDA
tDLCs
tCSTOs tCSTRh
Stop Condition Start Condition
tBUF
Note: In the timing tables the parameter name is added with an "o" for output signal timing and "i" for input signal timing. DS107
SCL
SDA
tDHCs
tCSTRs
Start Condition
tCSTRh
Note: In the timing tables the parameter name is added with an "o" for output signal timing
and "i" for input signal timing.
DS108