10 When the initialization ends, press the [CANCEL] button twice to return to the menu, select “7.Move Tape”, then press the [ENTER] button.

11 Use the V and v buttons to set the element address of the slot where the cleaning cartridge is set, then press the [ENTER] button.

Source 01 Destination DR

12

13

Make sure that “DR” is selected, then press the [ENTER] button.

When “[ENTER] to activate”

 

 

Source

01

appears, press the [ENTER] button. Destination

DR

[ENTER] to activate

The cleaning cartridge moves to the AIT drive, and cleaning begins. Cleaning takes about 30 seconds. (No message is displayed to indicate that cleaning is completed. Please wait for about 30 seconds.)

14 When cleaning is finished, use the Move Tape Menu to move the cleaning cartridge form the AIT drive to the AIT library.

15 Use the “Eject From Library” of the Eject/Insert Menu to take out the cleaning cartridge.

16 Press the [CANCEL] button three times to return to the status display.

Note

If an error message appears, perform one of the following.

When “Cleaning Tape at EOM” is displayed, a spent cleaning cartridge is set in the AIT drive. Replace the spent cleaning cartridge with a new one.

When “Clean failure” is displayed, cleaning failed. Repeat the cleaning procedure.

Chapter 5 Operating the AIT Drive