Error Messages

Current Share Error Codes

Current Share Error Codes

Table C.13Current Share Error Codes

Error

Error Message Description

code

 

+1900

Current Share General Error

 

 

+1911

Current share master already online

 

A unit on the CANbus network has already been assigned the current share

 

master unit. Only one is allowed per network.

+1912

Current share slave lost

 

One of the connected current share slaves have not responded in time.

+1921

Current share master lost

 

The assigned master has not responded in time.

 

 

+1922

Current share slave connection refused

 

Connection as a slave on the current share network has been refused due to

 

one of the following reasons:

 

4 slaves are already online,

 

the voltage rating does not match those of the master’s,

 

the current rating does not match those of the master’s.

 

 

+1924

Current share data out of range

 

The voltage or current readback or setpoint values passed are out of range.

+1925

Current share slave output off by unknown

 

One of the slave’s output is off because of unknown reasons

+1926

Current share slave output off by command

 

One of the slave’s output is off because of a command from a remote source

 

or the front panel.

+1927

Current share slave output off by AC fail

 

One of the slave’s output is off because of an AC fail condition.

 

 

+1928

Current share slave output off by OTP (Over Temperature Protection)

 

One of the slave’s output is off because of an OTP condition.

124

Operating Manual for Multichannel Functionality (GPIB-M)

Page 126
Image 126
Xantrex Technology GPIB-M-XHR, GPIB-M-XT, GPIB-M-XPD, GPIB-M-XFR3, GPIB-M-HPD manual Current Share Error Codes