Baldor GLC125, GLC35, GLC80 manual Action Description Display Comments, Are no active faults, Normal

Page 55

Display Modes The controller is in the display mode at all times except when in the programming mode. The display screens and menus may be selected by pressing the Enter or Exit keys to access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or Programming Menus. The LCD display shows the status of the generator output:

Operating Status The controller will power–up into an Emergency Stop failure mode, preventing possible engine operation. The controller must be manually reset before normal operation can be established. To reset the Emergency Stop condition, press the “OFF” push–button first, then press both “INCREMENT” and “ENTER” push–buttons simultaneously. The controller will then reset, if a remote emergency stop condition is not activated. The Utility Ready to Load programmable output will energize if the remote start contact is open. The Main LCD Display will be shown.

Action

Description

 

 

Display

 

 

Comments

 

 

 

 

 

 

 

 

Apply Power and

Main LCD Display.

 

 

 

 

 

 

Vavg

Aavg

Freq

 

 

Reset faults.

 

 

000

000

000

 

 

Press Enter key

Show Operating Status screens

 

 

 

 

 

Controller is in •Auto" position and there

 

 

 

 

 

 

UNIT READY

 

 

 

 

 

 

 

 

are no active faults.

Press or key

Scroll to next.

 

 

 

 

 

Controller is in •OFF" position from the

 

 

 

 

 

SWITCH IN OFF

 

 

 

 

 

 

 

front panel keypad push-button.

Press or key

Scroll to next.

 

 

 

 

 

Engine is running and all conditions are

 

 

 

 

 

UNIT RUNNING

 

 

 

 

 

 

 

normal.

Press or key

Scroll to next.

 

 

 

 

 

A shutdown fault is active. The specific

 

 

 

 

 

UNIT SHUTDOWN

 

 

 

 

 

fault will be automatically displayed.

Press or key

Scroll to next.

 

 

 

 

 

One or more faults are active. The

 

 

 

 

 

UNIT ALARM

 

 

 

 

 

 

 

display will automatically scroll through

 

 

 

 

 

 

 

all active faults at a two second rate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault Display The fault display menu is automatically displayed when an alarm or shutdown fault is activated. The specific alarm or shutdown fault label will be displayed and if multiple alarm conditions are present, the display will automatically scroll through all active faults.

MN2408

Operation 4-9

Image 55
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Warranty Period Limited WarrantyLabor Parts General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemSetting The Genset On An Existing Concrete Floor Slab Foundation Design Foundation ChecklistVibration Isolators Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationLevel Of Attenuation Exhaust System Exhaust ChecklistSystem Placement Multi-Engine InstallationsExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistCooling System Determination Heat ExchangerCooling System Design Engine Mounted Radiator Cooling Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorBackpressure must not exceed 20 of water column Hot Exhaust GassesGuidelines for Exhaust System Page Fuel Consumption Natural and LPG Fuel ConnectionsGeneral Considerations Natural Gas Connections Example Determining Pipe Size for Natural GasNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections General Wiring Considerations Battery Charger ConsiderationsFrame Ground Connection Page GLC125 Recommended Engine Oil and Battery TypePost Installation Checks GLC100Post Installation Checks Programming Keys Run SwitchOn when the OFF Switch is used to stop the engine Operator Control Panel Digital Engine Controller OnlyManual Start/Stop Operator Control PanelAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Engine Controller Inputs & Outputs Analog Faults Engine starter motor RunSuch as Fuel Rack Solenoids or electronic governors CrankNormal Are no active faultsAction Description Display Comments Front panel keypad push-buttonOther time delay functions are Vbc Displays the generators output voltage Phase system not applicableGenerator KVA Display Vab Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Span Calibration Repeat for each phaseDisplayed values Used Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function Oil PressureConfiguration Data Sheet Main Menu Loop Parameters Battery Voltage Fault Name Input Analog198 F Alarm Parameter Setting Volts A-BEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Verify the adjustments. Replace controller if failed Troubleshooting Guide Analog Controller OnlySpeed DIODE, 1N5408 Part numberGLC GLC125 Replacement PartsLAMP, #67, 12 Volt Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 No Load PowerName Address Phone Model Number Job Number Standby ContinuousProper belt alignment and tensions Adjust the AC voltage to match the normal sourceSwitch Are legibleBaldor District Offices Baldor Electric Company MN2408 04 FAR200