Baldor GLC80, GLC35, GLC50, GLC125 manual GLC Wire Size

Page 85

GLC Wire Size

 

 

 

 

 

 

 

 

 

 

Revision B

5–12–04

 

 

 

Circuit

Quantity per

Minimum

EDI Plant

Ampacity @125C

Breaker

Phase

Wire Gauge

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

15

1

#16

1

- #14 EPDM PER PHASE

40

20

1

#16

1

- #14 EPDM PER PHASE

40

30

1

#14

1

- #8 EPDM PER PHASE

90

40

1

#12

1

- #8 EPDM PER PHASE

90

50

1

#10

1

- #8 EPDM PER PHASE

90

60

1

#8

1

- #8 EPDM PER PHASE

90

70

1

#8

1

- #8 EPDM PER PHASE

90

80

1

#6

1

- #8 EPDM PER PHASE

90

90

1

#6

1

- #6 EPDM PER PHASE

125

100

1

#6

1

- #6 EPDM PER PHASE

125

110

1

#6

1

- #6 EPDM PER PHASE

125

125

1

#4

1

- #4 EPDM PER PHASE

170

150

1

#2

1

- #4 EPDM PER PHASE

170

175

1

#2

1

- #1 EPDM PER PHASE

265

200

1

#1

1

- #1 EPDM PER PHASE

265

225

1

1/0

1

- #1 EPDM PER PHASE

265

250

1

2/0

1

- #1/0 EPDM PER PHASE

305

300

1

4/0

1

- #2/0 EPDM PER PHASE

355

350

1

4/0

1

- #3/0 EPDM PER PHASE

410

400

2

#1

1

- #4/0 EPDM PER PHASE

475

450

2

1/0

2

- #1/0 EPDM PER PHASE

610

500

2

1/0

2

- #1/0 EPDM PER PHASE

610

600

2

3/0

2

- #2/0 EPDM PER PHASE

710

700

2

4/0

2

- #3/0 EPDM PER PHASE

820

800

3

2/0

2

- #4/0 EPDM PER PHASE

950

900

3

3/0

3

- #2/0 EPDM PER PHASE

1065

1000

3

3/0

3

- #3/0 EPDM PER PHASE

1230

1200

3

250

3

- #4/0 EPDM PER PHASE

1425

1400

4

4/0

4

- #4/0 EPDM PER PHASE

1900

1600

4

250

4

- #4/0 EPDM PER PHASE

1900

2000

5

250

5

- #4/0 EPDM PER PHASE

2375

2500

6

250

6

- #4/0 EPDM PER PHASE

2850

3000

7

250

6

- #250 EPDM PER PHASE

3180

4000

8

300

8

- #250 EPDM PER PHASE

4240

Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.

MN2408

Series GLC A-9

Image 85
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Warranty Period Limited WarrantyLabor Parts General Information MN2408 Site Planning Installation GuidelinesEngine Cooling System Controls and Transfer SwitchExhaust System Room AirSetting The Genset On An Existing Concrete Floor Slab Foundation Design Foundation ChecklistVibration Isolators Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationSystem Placement Exhaust System Exhaust ChecklistMulti-Engine Installations Level Of AttenuationExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistCooling System Determination Heat ExchangerCooling System Design Engine Mounted Radiator Cooling Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorBackpressure must not exceed 20 of water column Hot Exhaust GassesGuidelines for Exhaust System Page Fuel Consumption Natural and LPG Fuel ConnectionsGeneral Considerations Natural Gas Connections Example Determining Pipe Size for Natural GasNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections General Wiring Considerations Battery Charger ConsiderationsFrame Ground Connection Page Post Installation Checks Recommended Engine Oil and Battery TypeGLC100 GLC125Post Installation Checks On when the OFF Switch is used to stop the engine Run SwitchOperator Control Panel Digital Engine Controller Only Programming KeysManual Start/Stop Operator Control PanelAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownUtility Power Restored Utility Power Failure ConditionsUtility Normal Condition Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Such as Fuel Rack Solenoids or electronic governors RunCrank Engine starter motorAction Description Display Comments Are no active faultsFront panel keypad push-button NormalOther time delay functions are Generator KVA Display Phase system not applicableVab Displays the generators output voltage Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Span Calibration Repeat for each phaseDisplayed values Displays the type of calibration function Engine Temperature & Oil Pressure CalibrationOil Pressure UsedConfiguration Data Sheet Main Menu Loop Parameters 198 F Alarm Fault Name Input AnalogParameter Setting Volts A-B Battery VoltageEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Verify the adjustments. Replace controller if failed Troubleshooting Guide Analog Controller OnlySpeed DIODE, 1N5408 Part numberGLC GLC125 Replacement PartsLAMP, #67, 12 Volt Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Name Address Phone Model Number Job Number PowerStandby Continuous No LoadSwitch Adjust the AC voltage to match the normal sourceAre legible Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200