Baldor GLC35, GLC80, GLC50, GLC125 manual GLC Circuit Breaker & Electrical Data, Fla

Page 80

GLC Circuit Breaker & Electrical Data

 

Alternator

Engine

 

 

 

 

 

Output

 

 

 

 

GLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Model

Leads/

Fuel

Size

KW

Phase

Voltage

VAC

VAC

FLA

115%

Circuit

C.T.

Wire Size

 

Winding

Type

Rated

Config

(L - L)

(L - N)

FLA

Breaker

Ratio

(QTY) AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

4/06

Nat Gas

GM/8.1L

115

1

Series

240

120

479

551

600

600:5

(2) #2/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

125

3

// WYE

208

120

434

499

500

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

125

3

// WYE

220

127

410

472

500

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

125

3

Series/

240

120

376

432

450

500:5

(2) #1/0

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

130

3

// WYE

240

139

391

450

450

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

125

3

Series

380

220

237

273

300

300:5

(1) #2/0

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

 

 

3

 

416

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

Nat Gas

GM/8.1L

130

3

Series

480

277

195

225

225

250:5

(1) #1

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

4/06

Nat Gas

GM/8.1L

125

1

Series

240

120

521

599

600

600:5

(2) #2/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

130

3

// WYE

208

120

451

519

600

600:5

(2) #2/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

130

3

// WYE

220

127

426

490

500

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

130

3

Series/

240

120

391

450

450

500:5

(2) #1/0

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

130

3

// WYE

240

139

391

450

450

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

125

3

Series

380

220

237

273

300

300:5

(1) #2/0

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

 

 

3

 

416

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

Nat Gas

GM/8.1L

130

3

Series

480

277

195

225

225

250:5

(1) #1

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

4/06

LPG

GM/8.1L

105

1

Series

240

120

438

503

500

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

110

3

// WYE

208

120

382

439

450

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

110

3

// WYE

220

127

361

415

450

400:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

110

3

Series/

240

120

331

380

400

400:5

(2) #4/0

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

110

3

// WYE

240

139

331

380

400

400:5

(2) #4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

105

3

Series

380

220

199

229

250

250:5

(2) #1/0

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

 

 

3

 

416

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274E

12/311

LPG

GM/8.1L

110

3

Series

480

277

165

190

200

200:5

(1) #1

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

4/06

LPG

GM/8.1L

105

1

Series

240

120

438

503

500

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

110

3

// WYE

208

120

382

439

450

500:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

110

3

// WYE

220

127

361

415

450

400:5

(2) #1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

110

3

Series/

240

120

331

380

400

400:5

(2) #4/0

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

110

3

// WYE

240

139

331

380

400

400:5

(2) #4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

105

3

Series

380

220

199

229

250

250:5

(2) #1/0

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

 

 

3

 

416

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC125

UCI274F

12/311

LPG

GM/8.1L

110

3

Series

480

277

165

190

200

200:5

(1) #1

 

 

 

 

 

 

 

WYE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A-4 Series GLC

MN2408

Image 80
Contents GLC Generator California Proposition 65 Warning Table of Contents Generator AC Metering Engine Parameter Display Appendix aSection Product Safety Information Read This Manual ThoroughlySymbols OperationOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Labor Parts Limited WarrantyWarranty Period General Information MN2408 Installation Guidelines Site PlanningControls and Transfer Switch Engine Cooling SystemExhaust System Room AirVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab Weight Of The Genset Approximate Weight vs. kW OutputDesigning An Isolated Foundation Calculate Soil Bearing Load SBL CapacityTypical Foundation Installation Approximate Load Bearing Capacities of Various Soil TypesExhaust System Exhaust Checklist System PlacementMulti-Engine Installations Level Of AttenuationExhaust System Calculations Exhaust Piping Cooling System Cooling System Checklist Radiator CoolingCooling System Design Engine Mounted Radiator Cooling Heat ExchangerCooling System Determination Hot Well Installations Remote Radiator Cooling11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Air System Air System Checklist Wind BarrierEngine Crankcase Ventilation Transfer Switch Transfer Switch Checklist Transfer Switch LocationBattery Starting System Battery LocationBattery Charger Battery CablesGeneral Information MN2408 When the Generator is installed outdoors Generator LiftingMounting Dimensions Generator MountingSecure the Generator Ventilation TestGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel ConnectionsFuel Consumption Natural and LPG Natural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for Natural GasNatural Gas Connections Example Determining Pipe Size for LPG LP Gas Flow Rate Cubic Feet per Hour per Pipe LengthTransfer Switch Considerations RatingThree Phase WYE and Delta Connections Frame Ground Connection Battery Charger ConsiderationsGeneral Wiring Considerations Page Recommended Engine Oil and Battery Type Post Installation ChecksGLC100 GLC125Post Installation Checks Run Switch On when the OFF Switch is used to stop the engineOperator Control Panel Digital Engine Controller Only Programming KeysAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Fault Shutdown Automatic Mains Failure AMFUtility Power Failure Conditions Utility Power RestoredUtility Normal Condition Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Run Such as Fuel Rack Solenoids or electronic governorsCrank Engine starter motorAre no active faults Action Description Display CommentsFront panel keypad push-button NormalOther time delay functions are Phase system not applicable Generator KVA DisplayVab Displays the generators output voltage Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Displayed values Repeat for each phaseSpan Calibration Engine Temperature & Oil Pressure Calibration Displays the type of calibration functionOil Pressure UsedConfiguration Data Sheet Main Menu Loop Parameters Fault Name Input Analog 198 F AlarmParameter Setting Volts A-B Battery VoltageEngine Control Connections Operator Control Panel Analog Engine Controller Only 10 Analog Operator Control Panel11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Service Garretson Model KN Fuel Valve Considerations GeneralInstallation Section Troubleshooting and Maintenance EngineProblems and Solutions General Troubleshooting GuideTroubleshooting Guide Digital Controller Only Speed Troubleshooting Guide Analog Controller OnlyVerify the adjustments. Replace controller if failed Part number DIODE, 1N5408LAMP, #67, 12 Volt Replacement PartsGLC GLC125 Flywheel Housing Magnetic Pickup Cable Jam NutGLC Circuit Breaker & Electrical Data FLAGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Power Name Address Phone Model Number Job NumberStandby Continuous No LoadAdjust the AC voltage to match the normal source SwitchAre legible Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200