Baldor GLC80, GLC35, GLC50, GLC125 manual Main Menu Loop Parameters

Page 65

Figure 4-5 Main Menu Loop Parameters

Parameter

Setting

Range

System Voltage (Line To Line)

XXXXX VAC

120–15000VAC

System Frequency

50Hz/60Hz

Toggle Between 50/60 Hz

System Phases

1 Phase/3 Phase

Toggle Between 1 & 3 Phase

 

Neutral Connected

Toggle Between Yes/No

 

Voltage Sensing

Voltage Sensing Pt Ratio

 

Ratio XXX

Enter Number 1–208 (1=Direct)

 

Current Sensing

Current Sensing Ct Ratio

 

Ratio XXX

Enter Number 1–999 (1=Direct)

Temperature Scale

Deg C/Deg F

Toggle Between Deg C/Deg F

Pressure Scale

PSI/KPA

Toggle Between Psi/Kpa

Start Delay

XXX Seconds

0–999 Seconds

Crank Time

XX Seconds

0–99 Seconds

Rest Time

XX Seconds

0–99 Seconds

Starter Re–engage Delay

XX Seconds

0–99 Seconds 0=Disabled

Number Of Cranks

XX Cranks

0–99 Times 0=Continuous

Bypass Delay

XX Seconds

0–99 Seconds

Cool down Delay

XX Seconds

0–9999 Seconds

Nominal RPM

XXXX RPM

0–4000RPM

Flywheel Teeth (Engine Speed

XXX Teeth

0–999 Teeth

Sensing, Magnetic Pick Up

 

 

 

 

 

Crank Disconnect

XX %

0–100%

Overspeed

XX %

100–150%

Overspeed Transient

X.X Seconds

0.0–9.9 Seconds

Run Output

Fail Safe Yes/No

Toggle Between Yes/No

Loss Of Speed Signal

Shutdown Alarm/Shutdown

Toggle Between Alarm/Shutdown

Common Fail For

Not In Auto Yes/No

Toggle Between Yes/No

Horn For Not In Auto

 

Toggle Between Yes/No

Prog Output #1

 

Common Fail (Factory setting)

Prog Output #2

 

Common Fail (Factory setting)

Prog Output #3

 

Common Fail (Factory setting)

Prog Output #4

 

Common Fail (Factory setting)

Prog Output #5

 

Common Fail (Factory setting)

Prog Output #6

 

Common Fail (Factory setting)

Warm–up Delay

 

0–99 Seconds

Neutral Delay

 

0–99 Seconds

Return Delay

 

0–999 Seconds

Reset Run Hours

 

Access by Master Password Only

Yes/No

 

Toggle Between Yes/No

MN2408

Operation 4-19

Image 65
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Labor Parts Limited WarrantyWarranty Period General Information MN2408 Site Planning Installation GuidelinesEngine Cooling System Controls and Transfer SwitchExhaust System Room AirVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationSystem Placement Exhaust System Exhaust ChecklistMulti-Engine Installations Level Of AttenuationExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistCooling System Design Engine Mounted Radiator Cooling Heat ExchangerCooling System Determination Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel ConnectionsFuel Consumption Natural and LPG Natural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for Natural GasNatural Gas Connections LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Frame Ground Connection Battery Charger ConsiderationsGeneral Wiring Considerations Page Post Installation Checks Recommended Engine Oil and Battery TypeGLC100 GLC125Post Installation Checks On when the OFF Switch is used to stop the engine Run SwitchOperator Control Panel Digital Engine Controller Only Programming KeysAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownUtility Power Restored Utility Power Failure ConditionsUtility Normal Condition Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Such as Fuel Rack Solenoids or electronic governors RunCrank Engine starter motorAction Description Display Comments Are no active faultsFront panel keypad push-button NormalOther time delay functions are Generator KVA Display Phase system not applicableVab Displays the generators output voltage Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Displayed values Repeat for each phaseSpan Calibration Displays the type of calibration function Engine Temperature & Oil Pressure CalibrationOil Pressure UsedConfiguration Data Sheet Main Menu Loop Parameters 198 F Alarm Fault Name Input AnalogParameter Setting Volts A-B Battery VoltageEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Speed Troubleshooting Guide Analog Controller OnlyVerify the adjustments. Replace controller if failed DIODE, 1N5408 Part numberLAMP, #67, 12 Volt Replacement PartsGLC GLC125 Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Name Address Phone Model Number Job Number PowerStandby Continuous No LoadSwitch Adjust the AC voltage to match the normal sourceAre legible Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200