Baldor GLC125, GLC35, GLC80, GLC50 manual Navigation Hints

Page 59

Navigation Hints

Programming parameters are displayed in the same order as the Programming Sheets (see Figures 4-5 to 4-8). To skip over parameters that do not require changes, push and hold the ENTER push–button until the desired parameter is displayed. The EXIT push–button may be used to scroll backwards through the programming parameter loops.

To change a parameter value, use the INCREMENT or DECREMENT push–buttons to scroll through the available options or to adjust a value as desired and press the ENTER to accept the new value.

Note: If programming mode is terminated before the last change is accepted (pressing ENTER), that parameter value will remain unchanged.

Main Menu Loop The Main Menu Loop contains general system configuration programming such as system input voltages, currents, transformer ratios, as well as standard operating time delay functions.

System Voltage

Set to nominal system voltage as expressed in phase to phase voltage (i.e. a 347/600 volt system would be entered as

 

600). The programmable range of values is 120V-15,000V.

System Frequency

Set to nominal system frequency of either 50 HZ or 60 HZ.

System Phases

Set to match the power distribution system used on the generator set (i.e. either single phase or 3 phase system).

Neutral Connected

Set to Yes if generator's neutral conductor is connected to controller terminal TB1-VN and it is desired to display

 

line-neutral AC voltages for a 3 phase, 4 wire system.

Voltage Sensing Ratio

For direct voltage sensing wiring connections from 208 to 600 volts, enter 1 (i.e. a ratio of 1:1). When potential

 

transformers are utilized for voltage sensing, enter the calculated transformer ratio (e.g. when using 600:120

 

transformers, enter a number of 5).

Current Sensing Ratio

For current sensing wiring connections from current transformers (CT's), enter the calculated CT ratio (e.g. when using a

 

600:5 CT, enter a number of 120).

Temperature Scale

Select the desired units for engine temperature display and analog setpoints: Degrees Fahrenheit or Degrees Celsius.

 

Note: Alarm setpoints do not automatically re-configure when changing between Fahrenheit or degrees Celsius.

Pressure Scale

Select the desired units for engine pressure display and analog setpoints: Pounds per square inch (PSI) or Kilopascals

 

(KPA). Note: Alarm setpoints do not automatically re-configure when changing between PSI and KPA.

Start Delay

Select desired engine start delay time in seconds. If engine start delay is not required, set to zero. Note: If preheat and

 

or prelube functions are used, the engine start delay time should be set as required for these functions.

Crank Time

Select desired cranking time in seconds. If cycle cranking is selected, this time will be the crank time per attempt.

Rest Time

Select desired rest time between cranking attempts. (Only valid if multiple crank attempts are selected).

 

Note: This value will be ignored if only one attempt has been programmed.

Starter Re-Engage Duration This feature checks for a speed signal during cranking. If no speed signal is sensed, the controller assumes that the engine starter is not turning the engine over and disengages it after the programmed time delay, and re-engages it again. This process will repeat until a speed signal is sensed or cranking time expires, whichever occurs first.

If a speed signal is sensed, cranking continues until the engine starts or an overcrank condition occurs.

Set time in seconds as desired (i.e. a setting of 5 seconds will attempt cranking for 5 seconds after which time if no speed signal is detected, the crank output will be removed for a preset 1 second delay before re-engaging.)

Note: This action is more than a cycle cranking function and is independent of the number of attempts selected. Therefore, the •crank" time should be considered. To disable this feature, set to zero.

Number Of Crank Cycles Set to the number of cranking cycles required. (Zero will default to one.)

Bypass Delay

This setting is the time period that Alarm or Shutdown faults will be ignored after crank disconnect, allowing the engine to

 

settle into its normal operating mode (i.e. proper oil pressure, etc.). Typically 10 seconds.

Cool down Time

Set to desired cool down time in seconds. Up to 9999 seconds of cool down time may be programmed. Set to zero if not

 

required.

 

Note: If the controller is used in an AMF application it is recommended to set the cool down timer to a minimum of 10

 

seconds to allow the generator to transfer Off Load before enabling the cool down time. (Ensures the load is transferred

 

off of generator prior to stopping the engine.)

Nominal Engine RPM

Set to the nominal engine speed in revolutions per minute (RPM).

Flywheel Teeth

Set to the number of ring gear teeth on the engine flywheel. The magnetic pick-up must be installed to sense the same

 

teeth for speed sensing as programmed.

Crank Disconnect Speed Set crank disconnect speed in percentage of nominal speed, i.e. 30% or 540 RPM on an 1800 RPM engine.

Overspeed

Set overspeed shutdown point in percentage of nominal speed (i.e. 110% or 1980 RPM on an 1800 RPM engine).

Overspeed Transient Delay Select desired overspeed transient delay time in seconds. Time setting may be entered in tenths of seconds.

Run Output Fail-safe

When enabled (factory setting), this feature inhibits the run output until the controller receives a speed sensing signal.

 

This prevents possible damage caused by starting the engine with no speed sensing for crank disconnect and

 

overspeed. If selected, ensure that the speed signal is not less than 3.0VAC from the magnetic pick up while the engine

 

is cranking.

 

Note: If this feature is disabled, no overspeed protection or crank disconnect will be provided if the speed signal fails. If

 

you disable this feature Baldor strongly recommends that backup crank disconnect protection and additional overspeed

 

protection is provided.

MN2408

Operation 4-13

Image 59
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Labor Parts Limited WarrantyWarranty Period General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationLevel Of Attenuation Exhaust System Exhaust ChecklistSystem Placement Multi-Engine InstallationsExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistCooling System Design Engine Mounted Radiator Cooling Heat ExchangerCooling System Determination Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel ConnectionsFuel Consumption Natural and LPG Natural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for Natural GasNatural Gas Connections LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Frame Ground Connection Battery Charger ConsiderationsGeneral Wiring Considerations Page GLC125 Recommended Engine Oil and Battery TypePost Installation Checks GLC100Post Installation Checks Programming Keys Run SwitchOn when the OFF Switch is used to stop the engine Operator Control Panel Digital Engine Controller OnlyAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Engine Controller Inputs & Outputs Analog Faults Engine starter motor RunSuch as Fuel Rack Solenoids or electronic governors CrankNormal Are no active faultsAction Description Display Comments Front panel keypad push-buttonOther time delay functions are Vbc Displays the generators output voltage Phase system not applicableGenerator KVA Display Vab Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Displayed values Repeat for each phaseSpan Calibration Used Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function Oil PressureConfiguration Data Sheet Main Menu Loop Parameters Battery Voltage Fault Name Input Analog198 F Alarm Parameter Setting Volts A-BEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Speed Troubleshooting Guide Analog Controller OnlyVerify the adjustments. Replace controller if failed DIODE, 1N5408 Part numberLAMP, #67, 12 Volt Replacement PartsGLC GLC125 Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 No Load PowerName Address Phone Model Number Job Number Standby ContinuousProper belt alignment and tensions Adjust the AC voltage to match the normal sourceSwitch Are legibleBaldor District Offices Baldor Electric Company MN2408 04 FAR200