Baldor GLC80 Generator KVA Display, Vab Displays the generators output voltage, Amps a, Amps b

Page 57

Generator AC Metering The controller is in the display mode at all times except when in the programming mode. The display screens and menus may be selected by pressing the Enter or Exit keys to access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or Programming Menus. The LCD display shows the status of the generator output:

Generator Average Output Display

Vavg Aavg Freq

000 000 000

Average Voltage

Displays the average generator voltage as follows:

 

3-phase system: AVERAGE LINE TO LINE VOLTAGE--Phases

 

1-phase system: LINE TO LINE VOLTAGE--Phases A to B

Average Current

Displays the average generator current as follows:

 

3-phase system: AVERAGE LINE CURRENT--Phases A,B,C

 

1-phase system: AVERAGE LINE CURRENT--Phases A,B

Frequency

Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.

Generator KVA Display

 

KVA

 

 

 

632.23

 

 

 

 

 

KVA

Displays the generator's total power output in kilo-voltamperes (KVA).

Generator Phase Voltage Display (Line to Line)

Vab

Vbc

Vca

600

600

600

Vab

Displays the generator's output voltage:

 

3-phase system: LINE TO LINE VOLTAGE--Phases A to B

 

1-phase system: LINE TO LINE VOLTAGE--Phases A to B

Vbc

Displays the generator's output voltage:

 

3-phase system: LINE TO LINE VOLTAGE--Phases B to C

 

1-phase system: LINE TO NEUTRAL VOLTAGE--Phases A-N

Vca

Displays the generator's output voltage:

 

3-phase system: LINE TO LINE VOLTAGE--Phases C to A

 

1-phase system: LINE TO NEUTRAL VOLTAGE--Phases B-N

Generator Phase/Neutral Voltage Display (Line to Neutral)

Van

Vbn

Vcn

347

347

347

Note:

The generator's neutral must be connected to controller terminal TB1-VN and the •neutral connected" prompt in the main

 

program menu must be selected as •Yes".

Van

Displays generator voltage Phase A to Neutral.

Vbn

Displays generator voltage Phase B to Neutral.

Vcn

Displays generator voltage Phase C to Neutral.

Generator Phase Current Display

Amps a

b

c

408

451

415

Amps a

Displays generator load current as follows:

 

3-phase system: PHASE A CURRENT

 

1-phase system: PHASE A CURRENT

Amps b

Displays generator load current as follows:

 

3-phase system: PHASE B CURRENT

 

1-phase system: PHASE B CURRENT

Amps c

Displays generator load current as follows:

 

3-phase system: PHASE C CURRENT

 

1-phase system: not applicable

Generator Frequency/Hourmeter Display

FREQ

60.1 Hz

HOURS

56788 Hrs

FREQ

Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.

HOURS

Displays unit operating hours.

MN2408

Operation 4-11

Image 57
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Limited Warranty Warranty PeriodLabor Parts General Information MN2408 Site Planning Installation GuidelinesEngine Cooling System Controls and Transfer SwitchExhaust System Room AirFoundation Design Foundation Checklist Setting The Genset On An Existing Concrete Floor SlabVibration Isolators Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationSystem Placement Exhaust System Exhaust ChecklistMulti-Engine Installations Level Of AttenuationExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistHeat Exchanger Cooling System DeterminationCooling System Design Engine Mounted Radiator Cooling Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorHot Exhaust Gasses Backpressure must not exceed 20 of water columnGuidelines for Exhaust System Page Fuel Connections Fuel Consumption Natural and LPGGeneral Considerations Example Determining Pipe Size for Natural Gas Natural Gas ConnectionsNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Battery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Page Post Installation Checks Recommended Engine Oil and Battery TypeGLC100 GLC125Post Installation Checks On when the OFF Switch is used to stop the engine Run SwitchOperator Control Panel Digital Engine Controller Only Programming KeysOperator Control Panel Manual Start/StopAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownUtility Power Restored Utility Power Failure ConditionsUtility Normal Condition Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Such as Fuel Rack Solenoids or electronic governors RunCrank Engine starter motorAction Description Display Comments Are no active faultsFront panel keypad push-button NormalOther time delay functions are Generator KVA Display Phase system not applicableVab Displays the generators output voltage Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Repeat for each phase Span CalibrationDisplayed values Displays the type of calibration function Engine Temperature & Oil Pressure CalibrationOil Pressure UsedConfiguration Data Sheet Main Menu Loop Parameters 198 F Alarm Fault Name Input AnalogParameter Setting Volts A-B Battery VoltageEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Troubleshooting Guide Analog Controller Only Verify the adjustments. Replace controller if failedSpeed DIODE, 1N5408 Part numberReplacement Parts GLC GLC125LAMP, #67, 12 Volt Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Name Address Phone Model Number Job Number PowerStandby Continuous No LoadSwitch Adjust the AC voltage to match the normal sourceAre legible Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200