Baldor GLC125, GLC35, GLC80, GLC50 manual No Load Test

Page 51

No Load Test

To allow a timed No Load Test of the engine/generator set while using the AMF control application, a digital input contact from an external timer must be programmed for NO LOAD Test The sequence of operation for a No Load Test condition is as follows:

1.With the utility supply normal and the generator stopped, a no load test sequence may be initiated by closing an external exercise timer contact to the programmed digital input for No Load Test.

2.After the external exercise timer contact closes, the engine will start and come–up to normal operating speed and voltage. The controller will issue an alarm of a No Load Test condition. The connected transfer switch will remain on the utility and the generator will not transfer on load. Note: should the utility supply fail, the generator will automatically transfer on load.

3.The engine will continue to run as long as the external exercise timer contact remains closed.

4.After the external exercise timer contact opens, the engine will continue to run for its cool down time as programmed, then it will automatically stop.

Standard Faults When a fault occurs, information about the fault is displayed. The engine controller has many analog and digital inputs for monitoring and control operations. Three types of faults are used:

1.Internal Faults are derived from a combination of digital and analog inputs.

2.Digital Input Faults are initiated from external contact inputs.

3.Analog Input Faults are initiated from external analog signal inputs.

Figure 4-3 shows how the controller inputs and outputs are organized.

A description of each is provided.

Internal Faults

Overspeed Shutdown

Overspeed Shutdown is initiated when the engine's speed has increased above the overspeed setpoint. The overspeed fault

 

circuit is internally programmed as a latching shutdown fault. The overspeed shutdown fault circuit is programmable for the

 

percentage of nominal engine speed (i.e. overspeed setpoint) and for the transient time delay period. The programming

 

prompts for overspeed are located in the main menu programming loop.

Loss of Speed

Loss Of Speed is initiated when the engine's speed sensing circuit does not detect a speed signal for a period more than 2

Alarm/Shutdown

seconds following a run signal. The loss of speed fault may be user programmed as a latching shutdown fault or alarm only.

 

The programming prompts for loss of speed are located in the main menu programming loop.

Overcrank Shutdown

Overcrank Shutdown is initiated when the engine fails to start after the selected crank time or number of crank cycles. The

 

overcrank fault circuit is internally programmed as a latching shutdown fault and is not user programmable.

Switch not in AUTO

Switch not in AUTO is initiated when the controller's operating mode switch is changed from the auto position to any other

 

position (ON the keypad). This fault is internally programmed as a non latching alarm. In the main programming loop, this

 

alarm may be user programmed to initiate the common fail output relay.

Digital Input Faults

Four digital faults are provided and these are user programmable. Each digital fault input circuit is activated by a remote

Digital Inputs (N/O or N/C)

sensing contact that is external to the controller. Each digital fault input circuit may be programmed with a unique fault label

 

description as stored in the controller's non-volatile memory.

 

Factory settings have four standard digital faults as follows:

 

 

Fault

Fault

Digital Inputs

 

Name

Action

Terminal #

 

 

 

 

 

 

Low Oil Pressure

Shutdown

1

 

 

High Engine Temperature

Shutdown

2

 

 

Battery Charger Input Fail

Alarm

3

 

 

Low Fuel Level

Alarm

4

 

The

following is a list of all digital faults:

 

 

 

High Bearing Temp

Failed To Sync

Reverse Power

Bat Charger Input Fail

High Cooler Vibration

Low Fuel Press

Fail To Sync

Bat Chrg Trouble

High Engine Temp

Low Engine Temp

Vent Damper Fail

Bat Charger Fail

High Engine Vibration

Low Oil Pressure

Gen Breaker Open

DC Fail

High Fuel Level

Low Fuel Level

Ground Fault

Breaker Tripped

High Oil Level

Low Oil Level

No Load Test

Basin Rupture

High Oil Temp

Fuel Leak

ATS In Bypass

 

High Winding Temp

Low Fuel Press

Remote Emerg. Stop

 

*Highintkmanftemp

Low Coolant Level

Air Damper Tripped

 

•Blank" (i.e. no text for unused inputs)

MN2408

Operation 4-5

Image 51
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Limited Warranty Warranty PeriodLabor Parts General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemFoundation Design Foundation Checklist Setting The Genset On An Existing Concrete Floor SlabVibration Isolators Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationLevel Of Attenuation Exhaust System Exhaust ChecklistSystem Placement Multi-Engine InstallationsExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistHeat Exchanger Cooling System DeterminationCooling System Design Engine Mounted Radiator Cooling Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorHot Exhaust Gasses Backpressure must not exceed 20 of water columnGuidelines for Exhaust System Page Fuel Connections Fuel Consumption Natural and LPGGeneral Considerations Example Determining Pipe Size for Natural Gas Natural Gas ConnectionsNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Battery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Page GLC125 Recommended Engine Oil and Battery TypePost Installation Checks GLC100Post Installation Checks Programming Keys Run SwitchOn when the OFF Switch is used to stop the engine Operator Control Panel Digital Engine Controller OnlyOperator Control Panel Manual Start/StopAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Engine Controller Inputs & Outputs Analog Faults Engine starter motor RunSuch as Fuel Rack Solenoids or electronic governors CrankNormal Are no active faultsAction Description Display Comments Front panel keypad push-buttonOther time delay functions are Vbc Displays the generators output voltage Phase system not applicableGenerator KVA Display Vab Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Repeat for each phase Span CalibrationDisplayed values Used Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function Oil PressureConfiguration Data Sheet Main Menu Loop Parameters Battery Voltage Fault Name Input Analog198 F Alarm Parameter Setting Volts A-BEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Troubleshooting Guide Analog Controller Only Verify the adjustments. Replace controller if failedSpeed DIODE, 1N5408 Part numberReplacement Parts GLC GLC125LAMP, #67, 12 Volt Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 No Load PowerName Address Phone Model Number Job Number Standby ContinuousProper belt alignment and tensions Adjust the AC voltage to match the normal sourceSwitch Are legibleBaldor District Offices Baldor Electric Company MN2408 04 FAR200