Baldor GLC125, GLC35, GLC80, GLC50 manual Troubleshooting Guide Digital Controller Only

Page 75

Table 5-2 Troubleshooting Guide (Digital Controller Only)

Problem

Possible Cause

Remedy

 

 

 

Controller does not power up even with

Wiring Mistake

Check that there are no wiring errors/short circuits connected to the

correct DC power applied

 

controller.

 

Overload Condition

The MEC 20 contains an electronic fuse that trips when an overload

 

 

condition exists and does not reset until the supply voltage is

 

 

removed and reapplied after the overload condition is corrected.

LCD Display cannot be viewed

Microprocessor failure

Check that the controller's microprocessor is running by observing a

 

 

red flashing •watchdog" LED on the rear of the PCB. Replace

 

 

controller if failed.

 

Improper Supply Voltage

Check DC supply voltage at terminals B+ & B- (10-30VDC).

 

Improper contrast adjustment

Adjust LCD contrast potentiometer (R115) on rear of PCB for best

 

 

display.

 

 

 

Controller cannot be •Reset"

Engine not stopped

Verify the engine is at a complete stop before trying to reset.

 

Controller not in OFF mode

Set the controller to the OFF mode before trying to reset.

No •RUN" output signal

•Shutdown Faults" not reset

All shutdown faults must be reset (red shutdown LED must be off).

 

Engine speed not detected at cranking

Engine speed signal must be detected (speed signal green LED on)

 

 

during cranking if the •run-output fail safe" feature is enabled. Verify

 

 

correct magnetic pickup signal at cranking (2.0VAC min. during

 

 

cranking).

 

Run Contact not closing (terminals #18 & Check that the RUN output LED (on the rear of the PCB) is on.

 

#19)

If yes, verify relay contact operation on terminals #18 & #19.

 

 

Replace controller if failed.

Overspeed shutdown occurs at normal speed

Controller programmed values are wrong or controller has failed.

Verify the controller programmed values are correct for the number of flywheel teeth, nominal RPM, and overspeed setpoint percentage. Replace controller if failed.

Voltage or current metering is incorrect

Controller programmed values are wrong

Verify the controller programmed values are correct for the voltage

 

 

sensing PT ratio and/or current sensing CT ratio.

 

Ground is missing

Verify that the battery supply DC negative conductor is properly

 

 

grounded to the engine block (i.e. to a common ground point).

 

Analog input needs to be calibrated

Verify that the controller's analog input is properly calibrated.

 

Voltage sensing wiring mistake

Verify the voltage sensing wiring connection to the MEC 20 matches

 

 

power distribution type.

 

 

Note: standard direct voltage connection requires that the

 

 

generators neutral is solidly grounded.

Engine temperature or oil pressure

Analog input needs to be calibrated

Verify that the controller's analog input is properly calibrated.

display is incorrect

Failed engine sensor

Verify engine sensors.

 

 

Note: engine sensors must be factory supplied units only.

 

Ground is missing

Verify that the battery supply DC negative conductor is properly

 

 

grounded to the engine block (i.e. to a common ground point).

Engine temperature or oil pressure displays 9999

OR

Engine alarms are ON for high engine temperature or low oil pressure when engine is operating properly

Sending unit is disconnected (open

Verify the sending units wiring to controller terminals #37 & #38 (i.e.

circuit)

wiring is not open or shorted).

Defective sending unit

Verify the engine mounted senders have correct resistance values

 

for corresponding input temperature or pressure.

Wrong Temp or pressure calibration

Verify calibration.

Keypad Buttons (switches) do not

Keypad not connected to controller

Verify the interconnecting ribbon cable between the lexan faceplate

operate.

 

and main printed circuit board is correctly connected.

 

 

Replace controller if failed.

MN2408

Troubleshooting and Maintenance 5-3

Image 75
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Limited Warranty Warranty PeriodLabor Parts General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemFoundation Design Foundation Checklist Setting The Genset On An Existing Concrete Floor SlabVibration Isolators Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationLevel Of Attenuation Exhaust System Exhaust ChecklistSystem Placement Multi-Engine InstallationsExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistHeat Exchanger Cooling System DeterminationCooling System Design Engine Mounted Radiator Cooling Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorHot Exhaust Gasses Backpressure must not exceed 20 of water columnGuidelines for Exhaust System Page Fuel Connections Fuel Consumption Natural and LPGGeneral Considerations Example Determining Pipe Size for Natural Gas Natural Gas ConnectionsNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Battery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Page GLC125 Recommended Engine Oil and Battery TypePost Installation Checks GLC100Post Installation Checks Programming Keys Run SwitchOn when the OFF Switch is used to stop the engine Operator Control Panel Digital Engine Controller OnlyOperator Control Panel Manual Start/StopAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Engine Controller Inputs & Outputs Analog Faults Engine starter motor RunSuch as Fuel Rack Solenoids or electronic governors CrankNormal Are no active faultsAction Description Display Comments Front panel keypad push-buttonOther time delay functions are Vbc Displays the generators output voltage Phase system not applicableGenerator KVA Display Vab Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Repeat for each phase Span CalibrationDisplayed values Used Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function Oil PressureConfiguration Data Sheet Main Menu Loop Parameters Battery Voltage Fault Name Input Analog198 F Alarm Parameter Setting Volts A-BEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Troubleshooting Guide Analog Controller Only Verify the adjustments. Replace controller if failedSpeed DIODE, 1N5408 Part numberReplacement Parts GLC GLC125LAMP, #67, 12 Volt Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 No Load PowerName Address Phone Model Number Job Number Standby ContinuousProper belt alignment and tensions Adjust the AC voltage to match the normal sourceSwitch Are legibleBaldor District Offices Baldor Electric Company MN2408 04 FAR200