Baldor GLC50, GLC35, GLC80, GLC125 manual Battery Voltage/Engine Speed

Page 58

Engine Parameter Display Two engine operating parameter screens are provided.

Battery Voltage/Engine Speed

BATTERY

27.0 Vdc

 

(Tachometer)

 

SPEED

1800 rpm

 

 

 

 

 

Battery

Displays battery voltage in DC volts. The voltage is displayed with a resolution of 1/10 of a volt.

Speed

Displays engine speed in revolutions per minute (RPM).

Engine Temperature/Oil Pressure

ENG TEMP

57 Deg C

OIL PRESS

200 KPA

ENG TEMP

Displays engine temperature in either degrees Celsius or Fahrenheit (as selected).

OIL PRESS

Displays engine oil pressure in either pounds per square inch (PSI) or in Kilopascals (KPA) (as selected).

Program Menus The programming menu is used to change values such as time delays, analog fault settings, digital fault settings. Access to the programming sub–menus may only be obtained with a security password number. The sub menus are organized as follows:

Program Menu

PROGRAM MENU? NO

Displays two messages that may be toggled between YES and NO by pressing the INCREMENT push-button. NO Programming sub-menus are disabled when NO is displayed.

YES Programming sub-menus are enabled when YES is displayed and a valid password number is entered.

PASSWORD

0

Press INCREMENT or DECREMENT to change the password. Press ENTER when the correct number is displayed.

Read Only Mode

User can view the parameters but cannot change any values. The factory setting for this level is one (1).

Read / Write Mode

User can view and modify any parameter value. The factory setting for this level is two (2).

Master Read / Write Mode

User can view and modify any parameter value and view/modify the security password level numbers. Contact Baldor for master password if required.

The values of the parameter settings for your generator–set can be recorded for future reference using the Configuration Data Sheet shown in Figure 4-4.

After the correct password number is entered, the you may choose one of four programming menus. Press INCREMENT or DECREMENT to find the desired menu then press ENTER.

MAIN MENU LOOP

ANALOG FAULT MENU LOOP

DIGITAL FAULT MENU LOOP

CALIBRATION MENU LOOP

4-12 Operation

MN2408

Image 58
Contents GLC Generator California Proposition 65 Warning Table of Contents Generator AC Metering Engine Parameter Display Appendix aSection Product Safety Information Read This Manual ThoroughlySymbols OperationOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Warranty Period Limited WarrantyLabor Parts General Information MN2408 Installation Guidelines Site PlanningExhaust System Controls and Transfer SwitchEngine Cooling System Room AirSetting The Genset On An Existing Concrete Floor Slab Foundation Design Foundation ChecklistVibration Isolators Weight Of The Genset Approximate Weight vs. kW OutputDesigning An Isolated Foundation Calculate Soil Bearing Load SBL CapacityTypical Foundation Installation Approximate Load Bearing Capacities of Various Soil TypesMulti-Engine Installations Exhaust System Exhaust ChecklistSystem Placement Level Of AttenuationExhaust System Calculations Exhaust Piping Cooling System Cooling System Checklist Radiator CoolingCooling System Determination Heat ExchangerCooling System Design Engine Mounted Radiator Cooling Hot Well Installations Remote Radiator Cooling11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Air System Air System Checklist Wind BarrierEngine Crankcase Ventilation Transfer Switch Transfer Switch Checklist Transfer Switch LocationBattery Starting System Battery LocationBattery Charger Battery CablesGeneral Information MN2408 When the Generator is installed outdoors Generator LiftingMounting Dimensions Generator MountingSecure the Generator Ventilation TestBackpressure must not exceed 20 of water column Hot Exhaust GassesGuidelines for Exhaust System Page Fuel Consumption Natural and LPG Fuel ConnectionsGeneral Considerations Natural Gas Connections Example Determining Pipe Size for Natural GasNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPG LP Gas Flow Rate Cubic Feet per Hour per Pipe LengthTransfer Switch Considerations RatingThree Phase WYE and Delta Connections General Wiring Considerations Battery Charger ConsiderationsFrame Ground Connection Page GLC100 Recommended Engine Oil and Battery TypePost Installation Checks GLC125Post Installation Checks Operator Control Panel Digital Engine Controller Only Run SwitchOn when the OFF Switch is used to stop the engine Programming KeysManual Start/Stop Operator Control PanelAutomatic Start/Stop Automatic Fault Shutdown Automatic Mains Failure AMFUtility Normal Condition Utility Power Failure ConditionsUtility Power Restored Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Crank RunSuch as Fuel Rack Solenoids or electronic governors Engine starter motorFront panel keypad push-button Are no active faultsAction Description Display Comments NormalOther time delay functions are Vab Displays the generators output voltage Phase system not applicableGenerator KVA Display Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Span Calibration Repeat for each phaseDisplayed values Oil Pressure Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function UsedConfiguration Data Sheet Main Menu Loop Parameters Parameter Setting Volts A-B Fault Name Input Analog198 F Alarm Battery VoltageEngine Control Connections Operator Control Panel Analog Engine Controller Only 10 Analog Operator Control Panel11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Service Garretson Model KN Fuel Valve Considerations GeneralInstallation Section Troubleshooting and Maintenance EngineProblems and Solutions General Troubleshooting GuideTroubleshooting Guide Digital Controller Only Verify the adjustments. Replace controller if failed Troubleshooting Guide Analog Controller OnlySpeed Part number DIODE, 1N5408GLC GLC125 Replacement PartsLAMP, #67, 12 Volt Flywheel Housing Magnetic Pickup Cable Jam NutGLC Circuit Breaker & Electrical Data FLAGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Standby Continuous PowerName Address Phone Model Number Job Number No LoadAre legible Adjust the AC voltage to match the normal sourceSwitch Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200