Baldor GLC125, GLC35, GLC80, GLC50 manual MN2408 Series GLC A-7

Page 83

GLC DATA Continued

 

Alternator

Engine

 

 

 

 

 

Output

 

 

 

 

GLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Model

Leads/

Fuel

Size

KW

Phase

Voltage

VAC

VAC

FLA

115%

Circuit

C.T.

Wire Size

 

Winding

Type

Rated

Config

(L - L)

(L - N)

FLA

Breaker

Ratio

(QTY) AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

4/06

Nat Gas

GM/4.3L

37

1

Series

240

120

154

177

175

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

39

3

// WYE

208

120

135

156

175

150:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

39

3

// WYE

220

127

128

147

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

39

3

Series/

240

120

117

135

150

150:5

(1) #4

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

40

3

// WYE

240

139

120

138

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

40

3

Series

380

220

76

87

90

100:5

(1) #6

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

 

 

3

 

416

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

Nat Gas

GM/4.3L

40

3

Series

480

277

60

69

70

75:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

4/06

LPG

GM/4.3L

41

1

Series

240

120

171

196

200

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

44

3

// WYE

208

120

153

176

175

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

44

3

// WYE

220

127

144

166

175

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

44

3

Series/

240

120

132

152

175

150:5

(1) #1

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

45

3

// WYE

240

139

135

156

175

150:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

45

3

Series

380

220

85

98

100

100:5

(1) #6

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

 

 

3

 

416

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC45

UCI224D

12/311

LPG

GM/4.3L

45

3

Series

480

277

68

78

80

75:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

4/06

Nat Gas

GM/4.3L

35

1

Series

240

120

146

168

175

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

// WYE

208

120

121

140

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

// WYE

220

127

115

132

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

Series/

240

120

105

121

125

125:5

(1) #4

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

// WYE

240

139

105

121

125

125:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

Series

380

220

66

76

80

75:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

 

 

3

 

416

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

Nat Gas

GM/4.3L

35

3

Series

480

277

53

61

60

60:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

4/06

LPG

GM/4.3L

35

1

Series

240

120

146

168

175

200:5

(1) #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

// WYE

208

120

121

140

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

// WYE

220

127

115

132

150

150:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

Series/

240

120

105

121

125

125:5

(1) #4

 

 

 

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

// WYE

240

139

105

121

125

125:5

(1) #4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

Series

380

220

66

76

80

75:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

 

 

3

 

416

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC35

UCI224C

12/311

LPG

GM/4.3L

35

3

Series

480

277

53

61

60

60:5

(1) #8

 

 

 

 

 

 

 

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MN2408

Series GLC A-7

Image 83
Contents GLC Generator California Proposition 65 Warning Table of Contents Appendix a Generator AC Metering Engine Parameter DisplayRead This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Labor Parts Limited WarrantyWarranty Period General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab Approximate Weight vs. kW Output Weight Of The GensetCalculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationApproximate Load Bearing Capacities of Various Soil Types Typical Foundation InstallationLevel Of Attenuation Exhaust System Exhaust ChecklistSystem Placement Multi-Engine InstallationsExhaust System Calculations Exhaust Piping Radiator Cooling Cooling System Cooling System ChecklistCooling System Design Engine Mounted Radiator Cooling Heat ExchangerCooling System Determination Remote Radiator Cooling Hot Well Installations11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Wind Barrier Air System Air System ChecklistEngine Crankcase Ventilation Transfer Switch Location Transfer Switch Transfer Switch ChecklistBattery Location Battery Starting SystemBattery Cables Battery ChargerGeneral Information MN2408 Generator Lifting When the Generator is installed outdoorsGenerator Mounting Mounting DimensionsVentilation Test Secure the GeneratorGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel ConnectionsFuel Consumption Natural and LPG Natural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for Natural GasNatural Gas Connections LP Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPGRating Transfer Switch ConsiderationsThree Phase WYE and Delta Connections Frame Ground Connection Battery Charger ConsiderationsGeneral Wiring Considerations Page GLC125 Recommended Engine Oil and Battery TypePost Installation Checks GLC100Post Installation Checks Programming Keys Run SwitchOn when the OFF Switch is used to stop the engine Operator Control Panel Digital Engine Controller OnlyAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Engine Controller Inputs & Outputs Analog Faults Engine starter motor RunSuch as Fuel Rack Solenoids or electronic governors CrankNormal Are no active faultsAction Description Display Comments Front panel keypad push-buttonOther time delay functions are Vbc Displays the generators output voltage Phase system not applicableGenerator KVA Display Vab Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Displayed values Repeat for each phaseSpan Calibration Used Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function Oil PressureConfiguration Data Sheet Main Menu Loop Parameters Battery Voltage Fault Name Input Analog198 F Alarm Parameter Setting Volts A-BEngine Control Connections 10 Analog Operator Control Panel Operator Control Panel Analog Engine Controller Only11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Garretson Model KN Fuel Valve Considerations General ServiceInstallation Engine Section Troubleshooting and MaintenanceGeneral Troubleshooting Guide Problems and SolutionsTroubleshooting Guide Digital Controller Only Speed Troubleshooting Guide Analog Controller OnlyVerify the adjustments. Replace controller if failed DIODE, 1N5408 Part numberLAMP, #67, 12 Volt Replacement PartsGLC GLC125 Cable Jam Nut Flywheel Housing Magnetic PickupFLA GLC Circuit Breaker & Electrical DataGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 No Load PowerName Address Phone Model Number Job Number Standby ContinuousProper belt alignment and tensions Adjust the AC voltage to match the normal sourceSwitch Are legibleBaldor District Offices Baldor Electric Company MN2408 04 FAR200