Baldor GLC50, GLC35, GLC80, GLC125 manual Battery Starting System, Battery Location

Page 30

6.Conduit, wire, circuit protective device sizes, insulation etc. must conform to applicable local and national codes and regulations.

7.Be certain to seal around conduits that penetrate the walls of the genset room to reduce the amount of noise that is transmitted to the surrounding areas of the building and maintain site fire code rating.

Battery Starting System

This section describes the battery starting system (nominal 12 volt rating of the battery supply) for the engine, battery charger, and precautions to take if the ambient temperature is expected to be below 70 °F (20°C).

WARNING: If batteries are not mounted in the battery rack supplied with the genset, protect batteries from vibration and do not locate them near a source of flame or spark. A battery presents a risk of fire and explosion because they generate hydrogen gas. Hydrogen gas is extremely explosive. Never jump start a battery, smoke in the area around the battery or cause any spark to occur in the area around the battery.

Battery Location

Locate batteries as close as possible to the genset to minimize starting circuit resistance, see Figure 2-18. High starting circuit resistance substantially reduces starting cranking ability. The genset data sheet lists the maximum allowable cranking system resistance. Mount batteries on a level rack away from dirt and liquids. Allow space for servicing (checking water level and level of charge). Baldor gensets can be ordered with battery racks already installed. Cold ambient temperature at the battery location substantially reduces the battery output.

Figure 2-18 Battery Starting System

Battery Size

The ability to start the engine depends upon battery capacity, ambient temperature and coolant and oil temperatures. The Engine/Generator Set Data Sheet lists minimum recommended battery capacity at various ambient temperatures. The recommended battery capacities are listed in the Electric Systems section of the Engine Data Sheet, cold cranking amps (CCA) at 0 °F (–18 °C).

Battery capacities decrease as ambient temperatures decrease so it is important to specify batteries with the appropriate CCA rating at a temperature no higher than the minimum ambient temperature for the application. Baldor requires thermostatically controlled coolant heaters on all after cooled standby gensets. After cooling is called out on the Engine Data Sheet under General Engine Data section as “aspiration“.

Oil pan immersion heaters are recommended for standby gensets housed outside where ambient temperatures may drop below 0 °F (–18 °C). Coolant heaters and oil pan immersion heaters are available from Baldor as factory installed options.

2-20 General Information

MN2408

Image 30
Contents GLC Generator California Proposition 65 Warning Table of Contents Generator AC Metering Engine Parameter Display Appendix aSection Product Safety Information Read This Manual ThoroughlySymbols OperationOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2408 Limited Warranty Warranty PeriodLabor Parts General Information MN2408 Installation Guidelines Site PlanningExhaust System Controls and Transfer SwitchEngine Cooling System Room AirFoundation Design Foundation Checklist Setting The Genset On An Existing Concrete Floor SlabVibration Isolators Weight Of The Genset Approximate Weight vs. kW OutputDesigning An Isolated Foundation Calculate Soil Bearing Load SBL CapacityTypical Foundation Installation Approximate Load Bearing Capacities of Various Soil TypesMulti-Engine Installations Exhaust System Exhaust ChecklistSystem Placement Level Of AttenuationExhaust System Calculations Exhaust Piping Cooling System Cooling System Checklist Radiator CoolingHeat Exchanger Cooling System DeterminationCooling System Design Engine Mounted Radiator Cooling Hot Well Installations Remote Radiator Cooling11 Valves & Fittings and Fluid Flow in Pipe Other Considerations 13 Coolant Mixture Air System Air System Checklist Wind BarrierEngine Crankcase Ventilation Transfer Switch Transfer Switch Checklist Transfer Switch LocationBattery Starting System Battery LocationBattery Charger Battery CablesGeneral Information MN2408 When the Generator is installed outdoors Generator LiftingMounting Dimensions Generator MountingSecure the Generator Ventilation TestHot Exhaust Gasses Backpressure must not exceed 20 of water columnGuidelines for Exhaust System Page Fuel Connections Fuel Consumption Natural and LPGGeneral Considerations Example Determining Pipe Size for Natural Gas Natural Gas ConnectionsNatural Gas Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPG LP Gas Flow Rate Cubic Feet per Hour per Pipe LengthTransfer Switch Considerations RatingThree Phase WYE and Delta Connections Battery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Page GLC100 Recommended Engine Oil and Battery TypePost Installation Checks GLC125Post Installation Checks Operator Control Panel Digital Engine Controller Only Run SwitchOn when the OFF Switch is used to stop the engine Programming KeysOperator Control Panel Manual Start/StopAutomatic Start/Stop Automatic Fault Shutdown Automatic Mains Failure AMFUtility Normal Condition Utility Power Failure ConditionsUtility Power Restored Load Test Push-button OperationNo Load Test Engine Controller Inputs & Outputs Analog Faults Crank RunSuch as Fuel Rack Solenoids or electronic governors Engine starter motorFront panel keypad push-button Are no active faultsAction Description Display Comments NormalOther time delay functions are Vab Displays the generators output voltage Phase system not applicableGenerator KVA Display Vbc Displays the generators output voltageBattery Voltage/Engine Speed Navigation Hints Main Menu Loop Voltage Calibration Procedure Repeat for each phase Span CalibrationDisplayed values Oil Pressure Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function UsedConfiguration Data Sheet Main Menu Loop Parameters Parameter Setting Volts A-B Fault Name Input Analog198 F Alarm Battery VoltageEngine Control Connections Operator Control Panel Analog Engine Controller Only 10 Analog Operator Control Panel11 9957N Analog Engine Controller Connections 12 A121H Analog Engine Controller Connections Service Garretson Model KN Fuel Valve Considerations GeneralInstallation Section Troubleshooting and Maintenance EngineProblems and Solutions General Troubleshooting GuideTroubleshooting Guide Digital Controller Only Troubleshooting Guide Analog Controller Only Verify the adjustments. Replace controller if failedSpeed Part number DIODE, 1N5408Replacement Parts GLC GLC125LAMP, #67, 12 Volt Flywheel Housing Magnetic Pickup Cable Jam NutGLC Circuit Breaker & Electrical Data FLAGLC Data 259 300 MN2408 Series GLC A-7 144 150 GLC Wire Size Figure A-2 Customer Interface Connection Diagram MN2408 Series GLC A-11 Figure A-4 Single Phase w/o Breaker Connection Diagram Figure A-5 Single Phase One Breaker Connection Diagram Figure A-6 Single Phase Two Breaker Connection Diagram MN2408 Series GLC A-15 Series GLC MN2408 MN2408 Series GLC A-17 Series GLC MN2408 Figure A-11 Three Phase Connection Diagram Figure A-12 Three Phase Connection Diagram with PMG MN2408 Series GLC A-21 Series GLC MN2408 MN2408 Series GLC A-23 Series GLC MN2408 MN2408 Series GLC A-25 Series GLC MN2408 MN2408 Series GLC A-27 Figure A-20 Control Box Connections with MEC2 Controller Figure A-21 Engine Wiring, Woodward 4.3L GM Figure A-22 Engine Wiring, Woodward 5.7L GM Figure A-23 Engine Wiring, Woodward 8.1L GM Series GLC MN2408 Standby Continuous PowerName Address Phone Model Number Job Number No LoadAre legible Adjust the AC voltage to match the normal sourceSwitch Proper belt alignment and tensionsBaldor District Offices Baldor Electric Company MN2408 04 FAR200