15. Press the to advance to the next parameter, COMMS PARITY.

 

 

 

 

COMMS PARITY

 

 

 

 

 

 

 

ODD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

to change, then

to

Selections

 

 

 

 

 

 

NONE ODD EVEN

desired choice, then press the

.

 

 

 

 

 

 

 

 

 

 

16. Press the to advance to the next parameter, INPUT SCAN SEQUENCE

INPUT SCAN SEQUENCE

8 INPUTS-2 SCANS/SEC

I

N S T R

S E T T I N G S

&

Selections

8 INPUTS-2 SCANS/SEC

4 INPUTS-4 SCANS/SEC 2INP-4S/S, 4INP-2S/S 1INP-8S/S, 2INP-4S/S 1INP-8S/S, 4INP-2S/S 2I-4S, 2I-2S, 4I-1S 1I-8S, 1I-4S, 2I-2S 1I-8S, 1I-4S, 4I-1S 1I-8S, 2I-2S, 4I-1S 1I-8S, 1I-2S, 6I-1S

Press the

to change, then

to

desired choice, then press the .

D E R I V E D

The input scan rate is programmable and dependant on the number of active inputs present. The total scans per second for the instrument is 16 scans/second, and the instrument can have up to 8 inputs configured. INPUT SCAN SEQUENCE prompt allows the scan rate to be changed. Select the scan rate closest to the rate required. NOTE: The total of inputs must be equal to or greater than the actual number of inputs configured.

Example:

4 Inputs Configured

 

 

Require One input scan of 8/sec

 

One input scan of 4/sec

 

Two inputs scan of 1/sec each

 

Select: 1I-8S, 1I-4S,

4I-1S

 

IV1 is 8 scans/sec, IV2 is 4 scans/sec and IV3 through

 

IV6 are 1 scan/sec. Note that it does no harm to include

 

unused inputs in the scan sequence as they will be

 

ignored

 

 

 

 

Section 4

4-81

Edition 3