6.Press the to advance to the next parameter, OUTPUT 1 HYSTERESIS (only seen if OUT 1 TYPE is ON/OFF).

NOTE: Units correspond to Units configured in Process Variables

Cx OUT 1 HYSTERESIS

3 UNITS

Press the to change, then or

to desired number, then press the .

Note: Hysteresis centers on the control setpoint.

Selections

0 to 999999

(decimal position = 0)

0 to 9.9999

(decimal position = 4)

7.Press the to advance to the next parameter, OUTPUT 2 HYSTERESIS (only seen if OUT 2 TYPE is ON/ OFF).

NOTE: Units correspond to Units configured in Process Variables

Cx OUT 2 HYSTERESIS

3 UNITS

Press the to change, then or

to desired number, then press the .

Note: Hysteresis centers on the control setpoint.

Selections

0 to 999999

(decimal position = 0)

0 to 9.9999

(decimal position = 4)

8.Press the to advance to the next parameter, OUTPUT 1 PERCENT UPPER LIMIT (only seen if OUT 1 TYPE is PID).

Cx OUT 1 PERCENT

 

Press the

to change, then

or

UPPER LIMIT

100%

to desired choice, then press the

.

 

 

Selections

1 to100

Edition 3

13-6

Section 13

Rev G

Page 240