Anderson Manufacturing AV-9000 manual Cx Copy from Contrlr, Cx SP Ramp Rate Units/HR, 13-32

Models: AV-9000

1 321
Download 321 pages 29.81 Kb
Page 266
Image 266

2. Press the to advance to the next parameter, COPY/INITIALIZE.

Cx COPY/INITIALIZE

NO

Selections

YES or NO

Press the to change, then or

to desired selection, then press the .

If selection is NO, see Step 3.

If selection is YES:

Cx COPY FROM CONTRLR

(0=INITIALIZE)X

Input to be copied from

0=FACTORY DEFAULT

Press the or to the control number to be

copied from

3. Press the to advance to the next parameter, SETPOINT RAMP RATE.

Note: Units correspond to Units configured in Process Variables.

Cx SP RAMP RATE

0 units/HR

Selections

0 to 999999

Press the to change, then or(decimal position=0) 0 to 9.9999

(decimal position=4)

to desired number, then press the .

RAMP RATE dampens the rate at which the control algorithm will ramp to the control setpoint. If the setpoint changes abruptly from one value to another, an internal setpoint will be ramping to the selected setpoint (SP1, SP2, or Remote) at the rate selected in Cx SP RAMP RATE. The internal setpoint is viewable by setting the ramped setpoint parameter, Cx DISPLAY RAMPED SP located in CONTROLLERS section to something other than NOT DISPLAYED.

Edition 3

13-32

Section 13

Rev G

 

 

Page 266
Image 266