6. Upon selection of YES, the chart is initialized and the unit exits to the NORMAL DISPLAY if Chart Rotation and Trend Data Collect are ON. If either Chart Rotation or Trend Data Collect are OFF, after the initialization message, the unit will display CHART ROTATION OFF and/or TREND DATA COLLECT OFF, as applicable, until any key is pressed. This is a reminder that normal recording will not commence.

6.2 CHART CONFIGURATION

To enter Chart configuration, from the Normal Display, press the until SELECT appears in the upper

display line and CHART CONFIGURATION appears in the lower display line. If CHART KEY DISABLED ap- pears in the lower display line, refer to Section 9, Enables and Passwords, for instructions to enable Chart Prompts. If PASSWORD appears in the lower display line, the correct "password" will need to be entered before access to the Chart Select is allowed.

1. Press the to display CHART SIZE.

Note: When changing

 

 

 

 

CHART SIZE

 

 

 

chart size, calibration of

 

 

 

 

 

 

 

the instrument to the

 

 

 

 

 

 

 

 

 

chart is required. See

 

 

 

 

12in

 

 

 

chart calibration in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section 11.

 

 

 

 

 

Press the

to change, then

to

 

 

 

 

 

 

 

 

Selection

 

 

10in

11in

12in

desired choice, then press the

.

 

 

 

 

 

 

 

2. Press the to advance to the next parameter, CHART TYPE USED.

CHART TYPE USED

RINGS ONLY

Selection

RINGS/LINES/SCALES RINGS AND TIMELINES RINGS ONLY

Press the to change, then to

desired choice, then press the .

Edition 3

6-2

Section 6

Rev G

Page 194
Image 194