Anderson Manufacturing AV-9000 High Peak Input Prompt Dvxx Input Actuator Reset YES, Reset Output

Models: AV-9000

1 321
Download 321 pages 29.81 Kb
Page 115
Image 115

10.HIGH SELECT and LOW SELECT

 

INPUT 1:

A

PROMPT:

DVxx INPUT A

 

INPUT 2:

B

PROMPT:

DVxx INPUT B

 

ACTUATOR:

n/a

 

 

 

 

RESET:

n/a

 

 

 

 

OUTPUT:

= HIGHER of A and B

for HIGH SELECT

 

 

= LOWER of A and B

for LOW SELECT

11.

HIGH PEAK

 

 

 

 

 

INPUT 1:

A

PROMPT:

DVXX INPUT

 

ACTUATOR:

n/a

 

 

 

 

RESET:

YES

PROMPT:

DVxx RESET ACTUATOR

 

OUTPUT:

= HIGHEST VALUE of A since last RESET

 

 

Whenever RESET is active, the HIGHEST VALUE will be the current value of A.

12.

LOW PEAK

 

 

 

 

 

INPUT 1:

A

PROMPT:

DVxx INPUT

 

ACTUATOR:

n/a

 

 

 

 

RESET:

YES

PROMPT:

DVXX RESET ACTUATOR

 

OUTPUT:

= LOWEST VALUE of A since last RESET.

 

 

Whenever RESET is active, the LOWEST VALUE will be the current value of A.

13.TRACK AND HOLD

INPUT 1:

A

PROMPT:

DVxx INPUT

ACTUATOR:

YES

PROMPT:

DVxx TRACK ACTUATOR

RESET:

n/a

 

 

OUTPUT:

= Current value of A if the state of the Selected Actuator is true

=Last value of A when the state of the Selected Actuator changed from true to false

14.1 of 2 SELECTOR

INPUT 1:

A

PROMPT:

DVxx INPUT A

INPUT 2:

B

PROMPT:

DVxx INPUT B

ACTUATOR:

YES

PROMPT:

DVxx SELECT B ACTUAT

RESET:

n/a

 

 

OUTPUT:

= A if the state of the Selected Actuator is false.

=B if the state of the Selected Actuator is true.

15.CONVERT ACTUATOR

ACTUATOR:

YES

PROMPT:

DVxx ACTUATOR

RESET:

n/a

 

 

OUTPUT:

= 0.0 if the state of the Selected Actuator is false

=1.0 if the state of the Selected Actuator is true.

16.CONVERT F TO C

INPUT 1:

A

PROMPT:

DVxx INPUT°F

ACTUATOR:

n/a

 

 

RESET:

n/a

 

 

OUTPUT:

= (A-32) * 5/9

 

 

 

 

 

 

Edition 3

 

4-30

Section 4

Rev G

Page 115
Image 115
Anderson Manufacturing AV-9000 High Peak Input Prompt Dvxx Input Actuator Reset YES, LOW Peak Input Prompt, Reset Output