27.Press the to advance to the next parameter, LOOP ALARM TIME (only seen if CONTROL LOOP OPEN selected as ALARM TYPE and ON/OFF selected as CONTROL TYPE).

 

 

 

 

PVx LOOP ALARM TIME

 

 

 

 

 

 

60 SECONDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

to change, then

to

Selections

 

 

 

 

1 - 9999

desired number, then press the

.

 

 

 

 

28.Press the to advance to the next parameter, ALARM INHIBIT (only seen if an Alarm has been configured).

PVx LOOP ALARM INHIBIT

NO

Selections

NO YES

Press the

to change, then

to

desired choices, then press the .

On power-up, an "alarm" condition may occur, based on the alarm value, the process variable value and, if appropriate to the alarm type, the (active) setpoint value. This would normally activate the alarm; however; if the pertinent alarm is inhibited, the alarm indication is suppressed and the alarm will remain inactive. This will prevail until the "alarm" condition returns to the "inactive" state, whereafter the alarm will operate normally.

29. Press the

and the display advances to the next process variable input to be programmed. Refer to

the beginning of this section, page 4-32.