17.CONVERT C TO F

 

INPUT 1:

A

PROMPT:

DVxx INPUT°C

 

ACTUATOR:

n/a

 

 

 

RESET:

n/a

 

 

 

OUTPUT:

= (A * 9/5) +32

 

 

18.

BTU

 

 

 

 

INPUT 1:

F

PROMPT:

DVxx FLOW

 

INPUT 2:

TEMPH

PROMPT:

DVxx HIGHER TEMP

 

INPUT 3:

TEMPL

PROMPT:

DVxx LOWER TEMP

 

INPUT 4:

C

PROMPT:

DVxx SCALING CONST.

 

ACTUATOR:

n/a

 

 

 

RESET:

n/a

 

 

 

OUTPUT:

= C*F* (TEMPH-TEMPL)

 

 

 

If INPUT 4 is "NOT USED", then C=1

 

 

NOTES:

F - Flow

 

 

 

 

TEMPH - Higher Temperature for DeltaT

 

 

 

TEMPL - Lower Temperature for DeltaT

 

 

 

C - Scaling Constant

 

The Temperatures can be degrees F or C, but the scaling constant must take this into account.

19.ADD

 

INPUT 1:

A

PROMPT:

DVxx INPUT 1

 

INPUT 2:

B

PROMPT:

DVxx INPUT 2

 

INPUT 3:

C

PROMPT:

DVxx INPUT 3

 

INPUT 4:

D

PROMPT:

DVxx INPUT 4

 

ACTUATOR:

n/a

 

 

 

RESET:

n/a

 

 

 

OUTPUT:

= A+B+C+D

 

 

20.

AVG

 

 

 

 

INPUT 1:

A

PROMPT:

DVxx INPUT 1

 

INPUT 2:

B

PROMPT:

DVxx INPUT 2

 

INPUT 3:

C

PROMPT:

DVxx INPUT 3

 

INPUT 4:

D

PROMPT:

DVxx INPUT 4

 

ACTUATOR:

n/a

 

 

 

RESET:

n/a

 

 

 

OUTPUT:

= (A+B+C+D)/E

 

 

Where E is the number of inputs that are CONFIGURED.

Section 4

4-31

Edition 3

Rev G

Page 116