10.5 CHART DEMONSTRATION

Allows the user to demonstrate the chart capabilites. CAUTION: When this "TEST" is intiated, any parameter values previously programmed will be replaced with the demonstration values.

Step 1

With CHART DEMONSTRATION in the lower display line, depress the , INITIATE CHART DEMO appears in the upper display line and NO appears in the lower display line.

Step 2

Depress , select YES, depress . Instrument returns to Normal Display.

Step 3

Depress , CHANGE CHART appears in the upper display line, select YES, select YES again for

START NEW CHART.

Step 4

Chart demo begins.

Step 5

 

To exit or quit demo, depress

to CHART ROTATION and select OFF.

10.6 mA OUTPUT TEST

Allows the operator to verify that the current output(s) is/are functioning properly. A milliamp meter is required to perform this test.

Step 1

 

 

With mA OUTPUT in the lower display line, depress the

and INITIATE mA OUT TEST appears in the upper

display line and NO appears in the lower display line. Depress

, select YES, then depress

to start

the test.

 

 

Step 2

SELECT mA OUTPUT will appear in the upper display line and 1 2 3 4 will appear in the lower display line. To select output to be tested, depress the key directly under the desired output number.

Step 3

Connect the milliamp meter across the output terminals being tested. Be sure to observe proper polarity when

connecting the meter, terminal 1 is positive. Use

the

to increase or decrease the current output in

1 mA steps, from 0 to 22 mA.

 

 

 

 

 

 

 