Anderson Manufacturing AV-9000 S S, Ax3 Time Base, Per Sec, Ax3 Hysteresis, To Units configured

Models: AV-9000

1 321
Download 321 pages 29.81 Kb
Page 126
Image 126

20. Press the to advance to the next parameter, ALARM 3 TIME BASE (only seen if Ax3 TYPE is RATE).

Ax3 TIME BASE

PER SEC

P R O

Selections

PER SEC

PER MIN

PER HOUR

PER DAY

Press the to change, then ,

to desired choice, then press

the .

C E S S

V A

21. Press the to advance to the next parameter, ALARM 3 SAMPLE PERIOD (only seen if Ax3 TYPE is RATE).

 

 

 

 

Ax3 SAMPLE PERIOD

 

 

 

 

 

 

 

 

10 SECONDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

to change, then

to

Selections

 

 

 

 

 

 

1 to 9999 seconds

desired value, then press the

.

 

 

 

 

 

 

 

 

 

 

22. Press the to advance to the next parameter, ALARM 3 HYSTERESIS.

Note: Units correspond

Ax3 HYSTERESIS

 

 

to Units configured in

 

3 units

Process Variables.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

I

A B L E S

Selections

±999999

(decimal position = 0)

±9.9999

(decimal position = 4)

Press the to change, then to

desired value, then press the .

NOTE: If RATE Alarm is selected, Hysteresis equals RATE in units/TIME BASE.

Section 4

4-41

Edition 3

Rev G

Page 126
Image 126
Anderson Manufacturing AV-9000 manual S S, Ax3 Time Base, Per Sec, Ax3 Hysteresis, To Units configured