12.Press the to advance to the next parameter, OUTPUT 1 RATE (only if output 1 is proportional).

Cx OUT 1 RATE

0.00 MINUTES

Selections 0 to 100.00

Press the to change, then or

to desired number, then press the .

13.Press the to advance to the next parameter, OUTPUT 2 RATE (only if output 2 is proportional).

Cx OUT 2 RATE

0.00 MINUTES

Selections 0 to 100.00

Press the to change, then or

to desired number, then press the .

RATE attempts to anticipate rapid changes in system response and compensates before overshoot occurs. Rate can be applied at anytime, unlike auto reset which occurs within the integration band. The value is defined in minutes.

14.Press the and the display advances to the next controller to be tuned. Refer to the beginning of this section, page 13-31 .

Section 13

13-37

Edition 3

Rev G

Page 271