Anderson Manufacturing AV-9000 manual Cx OUT 1 Shift Units, Cx OUT 2 Shift Units, 13-34

Models: AV-9000

1 321
Download 321 pages 29.81 Kb
Page 268
Image 268

6. Press the to advance to the next parameter, OUTPUT 1 SHIFT.

Note: Units correspond to Units configured in Process Variables.

Cx OUT 1 SHIFT

0 units

 

 

 

 

Selections

Press the

to change, then

or

 

0 to 999999

 

 

 

 

(decimal position=0)

 

 

 

 

0 to 9.9999

to desired number, then press the

 

.

(decimal position=4)

 

 

7. Press the to advance to the next parameter, OUTPUT 2 SHIFT (only if Output 2 is used).

Note: Units correspond to Units configured in Process Variables.

Cx OUT 2 SHIFT

0 units

 

 

 

 

Selections

Press the

to change, then

or

 

0 to 999999

 

 

 

 

(decimal position=0)

 

 

 

 

0 to 9.9999

to desired number, then press the

 

.

(decimal position=4)

 

 

OUTPUT SHIFT represents an offset of the on-off actuation points or proportional band relative to the normal position. For example, if two on-off outputs are being used, one for heating and one for cooling, and a deadband of 2is desired between the two, set OUT 1 SHIFT to -1 and set OUT 2 SHIFT to +1.