Chapter 1 Catalyst 6500 Series Switch Chassis Overview

Catalyst 6509-NEB Switch

Table 1-16 Catalyst 6509-NEB Switch Specifications

Item

Specification

 

 

Environmental

 

Temperature, operating

Certified for operation: 32° to 104°F (0° to 40°C)

 

Designed and tested for operation: 32° to 130°F (0° to 55°C)

 

Note The Catalyst 6500 series switches are equipped with internal air

 

temperature sensors that are triggered at 104°F (40°C) generating a

 

minor alarm and at 131°F (55°C) generating a major alarm.

Temperature, nonoperating

–4° to 149°F (–20° to 65°C)

and storage

 

Thermal transition

0.5°C per minute (hot to cold)

 

0.33°C per minute (cold to hot)

Humidity (RH), ambient

10% to 90%

(noncondensing) operating

 

Humidity (RH), ambient

5% to 95%

(noncondensing)

 

nonoperating and storage

 

Altitude, operating

Certified for operation: 0 to 6500 feet (0 to 2000 m)

 

Designed and tested for operation: –200 to 10,000 feet (–60 to 3000 m)

 

 

Physical Characteristics

 

Dimensions (H x W x D)

33.3 x 17.2 x 18.1 in. (84.6 x 43.7 x 46.0 cm).

 

Chassis requires 20 RU.

 

Chassis can be mounted in equipment racks that meet ANSI/EIA 310-D

 

and ETS 300-119 standards.

Weight

Chassis only: 55 lb (24.9 kg).

 

Chassis fully configured with 1 supervisor engine, 8 switching modules, and

 

2 power supplies: 135 lb (61.2 kg).

 

 

Airflow

WS-C6509-NEB-FAN (standard fan tray)—294 CFM

 

Optional high-speed fan tray1—630 CFM

 

Note To maintain proper air circulation through the Catalyst switch

 

chassis, we recommend that you maintain a minimum 6-inch (15 cm)

 

separation between a wall and the chassis air intake or a wall and the

 

chassis air exhaust. You should also allow a minimum separation of

 

12 inches (30.5 cm) between the hot air exhaust on one chassis and

 

the air intake on another chassis. Failure to maintain adequate air

 

space can cause the chassis to overheat and the system to fail. On

 

Catalyst chassis in which the airflow is from front to back, the

 

chassis may be placed side-by-side.

 

 