Environmental

 

 

NOTE: Outside the standard operating

 

 

temperature (10 °C to 35 °C), the system can

 

 

operate down to 5 °C or up to 40 °C for a

 

 

maximum of 10% of its annual operating hours.

 

For temperatures between 35 °C and 40 °C, de-rate

 

maximum allowable dry bulb temperature by 1 °C

 

per 175 m above 950 m (1 °F per 319 ft).

≤ 1% of annual operating hours

–5 °C to 45 °C at 5% to 90% RH with 26 °C dew

 

point.

 

 

NOTE: Outside the standard operating

 

 

temperature (10 °C to 35 °C), the system can

 

 

operate down to –5 °C or up to 45 °C for a

 

 

maximum of 1% of its annual operating hours.

 

For temperatures between 40 °C and 45 °C, de-

 

rate maximum allowable dry bulb temperature by 1

 

°C per 125 m above 950 m (1 °F per 228 ft).

Expanded operating temperature restrictions

• Do not perform a cold startup below 5 °C

 

• Install only 87 mm wide heat sinks

 

• Do not install more than 40 DIMMs

 

• The following do not support expanded

 

operating temperature range:

 

PCIe SSD

 

Express flash

 

LRDIMMs

 

– 130 W four-core processors

– Non Dell-qualified peripheral cards and/or peripheral cards greater than 25 W

80

Page 80
Image 80
Dell M820 owner manual For temperatures between 35 C and 40 C, de-rate