in the FM3/4 module. Therefore, in order to store the values in the FM module, the Auto-Tune values must be applied to the configuration file. When the user presses “Apply to Config.”, the values in the “Values From Drive” column are transferred into the Motor Parameters column. Then the values must be downloaded by downloading the entire configuration file using Device > Download.

Run Auto-Tune Button

The drive has the ability to run an Auto-Tune operation thereby measuring several different motor parameters. Doing so allows the drive to obtain certain parameters that are not typically provided by the motor manufacturer, and also optimizes other drive parameters to work properly with the connected motor/load.

PowerTools Pro allows the user to initiate the Auto-Tune feature from the Motor view.

The following table shows which parameters must be entered in order to run the Auto-Tune feature, and which parameters are measured by the Auto-Tune.

Motor Parameters

Needed to Run Auto-Tune

Measured by Auto-Tune Mode #

Motor Name

 

 

 

 

 

Peak Current

 

 

 

 

Continuous Current Rating

 

 

 

 

Motor Poles

 

 

 

 

Rotor Inertia

 

3

 

 

 

Motor Ke

 

3

 

 

 

Phase Resistance

 

2,3

 

 

 

Phase Inductance

 

2,3

 

 

 

Max Operation Speed

 

 

 

 

Encoder Lines/Rev

1,2,3

 

 

 

Encoder Lines/Rev Exponent

1,2,3

 

 

 

Encoder Marker Angle

 

1,2,3

 

 

 

Encoder U-Marker

 

1,2,3

 

 

 

Encoder Reference Motion

 

1,2,3

 

 

 

Encoder Type

 

 

 

 

 

Some Auto-Tunes cause motion while others do not. It is important to read and understand the warnings and instructions on the Auto-Tune windows. It is strongly recommended to unload the motor if Auto-Tune Mode #3 is commanded.

When online with the drive, to initiate an Auto-Tune, click RunAuto-Tune button. The Auto-Tune dialog box opens and contains warnings and instructions related to the Auto-Tune procedure, as well as selection of the Auto-Tune mode. An example of one of the Auto-Tune windows is shown in Figure 7.

10

Page 22
Image 22
Emerson P/N 400518-02 manual Run Auto-Tune Button