Setting Up Parameters

Faults View

Figure 15: Faults View - Online

Fault Enable Group

Low DC Bus Fault Enable

This parameter’s default setting is enabled. When enabled, the drive will detect a low DC bus at 60 Vdc and will log a Low DC Bus Fault if a power down is not completed after the low DC bus is detected. Clearing this check box will disable the Low DC Bus Voltage Fault. This will allow the drive to operate at a DC bus voltage below 60 Vdc as long as the logic power is supplied by the Alternate Power Supply (APS) with an Epsilon classic drive and a Logic Power Supply with the Epsilon EP-I drive.

Encoder State Fault Enable

This parameter’s default setting is enabled. When enabled, the drive will detect encoder state faults. Refer to Fault Codes in the Diagnostic and Troubleshooting section of this manual. The drive will not detect Encoder State faults when the fault is disabled. Disabling encoder faults is necessary for some types of programmable encoders when the state transitions are not always deterministic.

Commutation Hardware Fault Enable

When this checkbox is selected, faults occurring from the commutation tracks U, V, and W will be recognized as "E" faults in the drive. When this checkbox is clear, no fault will occur due to the commutation tracks. This functionality can be useful to diagnose the nature of the "E" fault. If the checkbox is clear and "E" faults are still occurring, then the encoder lines (A, A/, B, B/, Z, Z/) are the most likely source of the "E" fault.