Table 5. Alert Codes and Troubleshooting

Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer

alert button. Minor and Moderate alerts are found only in the Installer alert button.

 

 

 

Alert

 

 

 

Code

Priority

Alert Text

Steps to clear

 

 

 

 

10

Critical

(Stat) The thermostat has found an unknown

An unknown device is seen on the subnet in or outside of configuration mode. Clear by reconfiguring

 

 

device on the system.

the system. Press the setup tab, press start, and press confirm. If problem persists, then check all

 

 

 

DEVICE connections to make sure they are icomfort−compatible.

 

 

 

 

11

Critical

(Stat) The thermostat cannot find a previously

Check all connections and cycle system power. If problem persists, clear by reconfiguring the sys-

 

 

installed unit.

tem. Press the setup tab, press start, and press confirm. If problem persists, then check all DEVICE

 

 

 

connections to make sure they are icomfort−compatible.

 

 

 

 

12

Critical

(Stat) The thermostat cannot find an icomfort−

Thermostat did not find an Indoor Unit. Make sure there is an icomfort indoor unit on the system.

 

 

enabled indoor unit.

Check R, i+, i− and C connections, ohm wires and cycle power. Replace indoor unit control board if

 

 

 

there is no response.

 

 

 

 

14

Critical

(Stat) The thermostat found more than one ther-

Check wiring and remove duplicate equipment. Reconfigure system.

 

 

mostat, more than one indoor unit, or more than

 

 

 

one outdoor unit on the system.

 

 

 

 

 

18

Minor

(Stat) The outside temperature is below the lev-

Notification only − Outdoor Temp is below the Low Balance Point. Heat Pump will not be used to

 

 

el where the heat pump is programmed to heat

service a heating demand.

 

 

the home. The system will not use the heat

 

 

 

pump to warm your home.

 

 

 

 

 

19

Minor

(Stat) The outside temperature is higher than

Notification only − Outdoor Temp is above the High Balance Point. Indoor Unit (furnace or air−handler)

 

 

the level where the furnace or electric heat is

will not be used to service a heating demand.

 

 

programmed to work. The system will only use

 

 

 

the heat pump to warm your home.

 

 

 

 

 

29

Critical

(Stat) The thermostat is reading an indoor tem-

Indoor temperature rose above 99ºF during a heating or cooling demand. Heating operation is not

 

 

perature that is higher than 99ºF. The thermo-

allowed. Check to ensure that Heating Equipment is not stuck ON (reversing valve, etc.). Check the

 

 

stat will not allow any heating operation to begin

accuracy of the thermostat temperature sensor. Select cooling system mode to cool the indoor

 

 

until it senses a temperature lower than 99ºF.

space.

 

 

 

 

30

Moderate

(Stat) The thermostat is reading an indoor tem-

Indoor Temp fell below 40ºF. Cooling operation is not allowed. Check to ensure that cooling equip-

 

 

perature that is lower than 40ºF. The thermostat

ment is not stuck ON. Check accuracy of the thermostat temperature sensor. Select heating system

 

 

will not allow any cooling operation to begin un-

mode to heat the indoor space to above 40ºF.

 

 

til it senses a temperature higher than 40ºF.

 

 

 

 

 

31

Critical

(Stat) The thermostat has lost communication

[Indicated unit] has not communicated with thermostat for more than 3 minutes. Check connections.

 

 

with the (furnace, air−handler or outdoor unit) for

Ohm wires. If fault persists, then cycle power. Fault clears after communication is restored.

 

 

more than 3 minutes.

 

 

 

 

 

32

Moderate

(Stat) The (furnace, air−handler or outdoor unit)

[Indicated unit] is resetting itself. This event may occur during a power outage or power fluctuation in

 

 

is resetting itself.

the system. If persistent or if it coincides with the system operation then proceed with the following

 

 

 

steps. Check the power connections, check the amp draw at the transformer (the transformer maybe

 

 

 

overloaded) and check 24VAC voltage at the DEVICE. The alarm is only cleared by pressing the

 

 

 

clear button on the Installer Alerts Tab. If the fault persists after checking the connections, replace

 

 

 

the unit’s control board.

 

 

 

 

 

 

 

table continued on next page

Page 45

icomfort Wi-Fit 7−Day Programmable Communicating Thermostat

Page 45
Image 45
Lennox International Inc CBX32MV06, XP2101, XC2105, XC1702, XP1906, XP1702, SLP9801, G71MPP03 Alert Codes and Troubleshooting

FAQ

How do I clear an unknown device on the thermostat?

To clear an unknown device on the thermostat, reconfigure the system by pressing the setup tab, pressing start, and pressing confirm. If the problem persists, check all DEVICE connections to ensure they are icomfort compatible.

What should I do if the thermostat cannot find a previously installed unit?

Check all connections and cycle system power. If the problem persists, clear by reconfiguring the system. Press the setup tab, press start, and press confirm. If the problem persists, then check all DEVICE connections to ensure they are icomfort compatible.

What should I do if the thermostat cannot find an icomfort enabled indoor unit?

If the thermostat cannot find an icomfort enabled indoor unit, make sure there is an icomfort indoor unit on the system. Check R, i+, i and C connections, ohm wires, and cycle power. Replace indoor unit control board if there is no response.