Table 5. Alert Codes and Troubleshooting

Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer

alert button. Minor and Moderate alerts are found only in the Installer alert button.

 

 

 

Alert

 

 

 

Code

Priority

Alert Text

Steps to clear

 

 

 

 

180

Critical

(Furnace / Air Handler / Outdoor Unit) The ther-

In normal operation after control recognizes sensors, the alarm will be sent if valid temperature

 

 

mostat has found a problem with the (furnace,

reading is lost. Compare outdoor sensor resistance to temperature/resistance charts in unit installa-

 

 

air−handler or outdoor unit) outdoor sensor.

tion instructions. Replace sensor pack if necessary. At the beginning of (any) configuration, furnace

 

 

 

or air−handler control will detect the presence of the sensor(s). If detected (reading in range), ap-

 

 

 

propriate feature will be set as ’installed’ and shown in the ’About’ screen. The alarm/fault will clear

 

 

 

upon configuration, or sensing normal values.

 

 

 

 

200

Critical

(Furnace) The furnace rollout limit switch is

Correct the cause of rollout trip. Reset rollout switch. Reset power to clear. Test the furnace opera-

 

 

open.

tion. The alarm/fault clears after the furnace rollout switch is closed.

 

 

 

 

201

Critical

(Furnace / Air Handler) The system has lost

Lost communication with indoor blower motor. Possible causes include: power outage, brown−out,

 

 

communication with the (furnace or air−handler)

motor not powered, loose wiring, condensation on air handler control without cover on breaker.

 

 

indoor blower motor.

Problem may be on control or motor side. Cleared after communication is restored.

 

 

 

 

202

Critical

(Furnace / Air Handler) The unit size code for

Incorrect appliance unit size code selected. Check for proper configuring under Unit Size Codes for

 

 

the (furnace or air−handler) and the size of blow-

Furnace/Air Handler on configuration guide or in installation instructions. The alarm/fault clears after

 

 

er motor do not match.

the correct match is detected following a reset. Remove the thermostat from the system while apply-

 

 

 

ing power and reprogramming.

 

 

 

 

203

Critical

(Furnace / Air Handler) The unit size code for

No appliance unit size code selected. Check for proper configuring under: Unit Size Codes for Fur-

 

 

the (furnace or air−handler) has not been se-

nace/Air Handler on configuration guide or in installation instructions. Critical Alert. The alarm/fault

 

 

lected.

clears after the correct match is detected following a reset. Remove the thermostat from the system

 

 

 

while applying power and reprogramming.

 

 

 

 

204

Critical

(Furnace) There is a problem with the furnace

Check gas valve operation and wiring. The alarm/fault clears after the issue is corrected.

 

 

gas valve.

 

 

 

 

 

205

Critical

(Furnace) The furnace gas valve relay contact

Check wiring on control and gas valve. The alarm/fault clears after the issue is corrected.

 

 

is closed.

 

 

 

 

 

206

Critical

(Furnace) The furnace gas valve 2nd stage

Furnace will operate on 1st stage for the remainder of the heating demand. The alarm/fault will clear

 

 

relay is faulty.

after the issue is corrected. If unable to operate 2nd stage, replace control.

 

 

 

 

207

Critical

(Furnace) The furnace hot surface igniter is

Measure the resistance of hot surface igniter. Replace the it if it is not within the specified range

 

 

open.

found in IOM. The alarm/fault clears after the issue is corrected.

 

 

 

 

223

Critical

(Furnace) The furnace low pressure switch is

Check pressure (inches w.c.) of low pressure switch closing during a heat call. Measure operating

 

 

open.

pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

The alarm/fault clears after the issue is corrected.

 

 

 

 

224

Critical

(Furnace) The furnace low pressure switch is

Check operation of low pressure switch to see if it is stuck closed for longer than 150 seconds during

 

 

stuck closed.

a heat call . Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for

 

 

 

correct operation and restriction. The alarm/fault clears after the issue is corrected.

 

 

 

 

225

Critical

(Furnace) The furnace high pressure switch is

Check pressure (inches w.c.) of high pressure switch closing during a heat call. Measure operating

 

 

failing to close.

pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

The alarm/fault clears after the issue is corrected.

 

 

 

 

 

 

 

table continued on next page

506920−01 09/12

Page 48

Page 48
Image 48
Lennox International Inc XP2101, XC2105, XC1702, XP1906, XP1702, SLP9801, G71MPP03, SL28003 Alert Codes and Troubleshooting

FAQ

What are the critical alerts for the Lennox International Inc thermostat?

The critical alerts for the Lennox International Inc thermostat are displayed on the Home user screen, in the Homeowner alert button, and in the Installer alert button.

How do I clear the alert 180 for the furnace, air handler, or outdoor unit?

In normal operation after control recognizes sensors, the alarm will be sent if valid temperature reading is lost.

What should I do if the furnace rollout limit switch is open?

Correct the cause of the rollout trip and reset the power to clear. The alarm/fault clears after the furnace rollout switch is closed.