Lennox International Inc XP1702 Gas Heat Airflow Settings, Adjustable Parameters Table Installer

Models: CBX40UHV02 EL296V01 CBX32MV06 iComfort Wifi Thermostat SL28003 G71MPP03 SLP9801 XP1702 XP1906 XC1702 XC2105 XP2101

1 72
Download 72 pages 43.71 Kb
Page 40
Image 40
FURNACE

Table 3. Adjustable Parameters Table (Installer)

Parameter Name

Default

Min.

Max.

Incr.

Dependency

Note

Installer entry

 

 

 

 

 

 

 

 

FURNACE

Heating indoor blower OFF delay

DIP SW

60

180

10

None

DIP switch setting in

 

 

 

 

 

 

 

Non−comm.

 

 

 

 

 

 

 

 

 

Heating indoor blower ON delay

45 sec

15

45

5

None

45 sec fixed in Non−

 

 

 

 

 

 

 

Comm. IFC

 

 

 

 

 

 

 

 

 

Cooling indoor blower OFF delay

0 sec

0

30

2

Outdoor Unit

Not used on Non

 

 

 

 

 

 

present

Comm. IFC

 

 

 

 

 

 

 

 

 

Cooling indoor Blower ON Delay

2 sec

0

10

1

Outdoor Unit

2 sec fixed in Non−

 

 

 

 

 

 

present

Comm. IFC

 

 

 

 

 

 

 

 

 

Heat pump indoor blower OFF delay

45 sec

0

60

5

Heat Pump present

Not used on Non

 

 

 

 

 

 

 

Comm. IFC

 

 

 

 

 

 

 

 

 

Heat pump indoor blower ON delay

0 sec

0

30

5

Heat Pump present

Not used on Non

 

 

 

 

 

 

 

Comm. IFC

 

 

 

 

 

 

 

 

 

Gas Heat Airflow Settings

Heating Airflow Control Type (variable

0 – Fixed

0

1

1

DATS installed

0 (Fixed CFM)

 

capacity furnaces only)

CFM

1 (Fixed DAT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heating Airflow (CFM @ min.

DIP SW

 

 

25

 

 

 

heat)

 

 

Heating Airflow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Heating Airflow (CFM @ 100%

DIP SW

See furnace docu-

25

Control Type = 0

 

 

heat)

 

 

See furnace documen-

 

 

mentation (IOM or

 

 

 

Low Heating Discharge Air

 

 

 

tation (IOM or engineer-

 

 

engineering hand-

 

 

 

Temperature (DAT @ min heat)

DIP SW*

5

 

ing handbook) for size

 

book) for size spe-

 

 

 

 

 

(variable capacity furnaces only)

 

 

 

specific information

 

 

cific information

 

Heating Airflow

 

 

 

 

 

 

High Heating Discharge Air

 

 

 

 

Control Type = 1

 

 

Temperature (DAT @ 100% heat)

DIP SW*

 

 

5

 

 

 

(variable capacity furnaces only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* − Default DAT value is rounded to the closest number on 5 deg F resolution and limited by Minimum and Maximum value.

 

 

 

 

 

 

table continued on next page

506920−01 09/12

Page 40

Page 40
Image 40
Lennox International Inc XP1702, XP2101, XC2105 Gas Heat Airflow Settings, Adjustable Parameters Table Installer, Furnace

FAQ

What are the default values for adjustable parameters?

The default values for adjustable parameters can be found in the table on this page.

How to set the Heating indoor blower OFF delay?

The Heating indoor blower OFF delay can be set using the DIP switch settings in the table provided.

Where can I find the gas heat airflow settings for specific Lennox thermostat models?

The gas heat airflow settings for specific Lennox thermostat models can be found in the 'Gas Heat Airflow Settings' section of this page.