Table 5. Alert Codes and Troubleshooting | Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer | |||
alert button. Minor and Moderate alerts are found only in the Installer alert button. | ||||
|
|
| ||
Alert |
|
|
| |
Code | Priority | Alert Text | Steps to clear | |
|
|
|
| |
407 | Critical | (Outdoor Unit) The required amount of current is | Required amount of current is not passing through Run current transformer. Clears the error after | |
|
| not passing through run current transformer. | current is sensed in RUN sensor, or 1 normal compressor run cycle, or after power reset | |
|
|
|
| |
408 | Critical | (Outdoor Unit) The compressor is running con- | Compressor runs continuously. Clears the error after 1 normal compressor run | |
|
| tinuously. | cycle or after power reset. | |
|
|
|
| |
409 | Moderate | (Furnace / Air Handler / Outdoor Unit) The sec- | Secondary voltage is below 18VAC. After 10 minutes, operation is discontinued. | |
|
| ondary voltage for the (furnace, air−handler or | Clears the code after voltage is higher than 20 VAC for 2 seconds or after power | |
|
| outdoor unit) has fallen below 18VAC. If this | reset. | |
|
| continues for 10 minutes, the thermostat will |
| |
|
| turn off the (furnace, air−handler or outdoor unit). |
| |
|
|
|
| |
410 | Moderate | (Outdoor Unit) The outdoor unit pressure is be- | Unit pressures are below the lower limit. Pressure switch opens at 40 psig (system shuts down) and | |
|
| low the required limit. | closes at 90 psig (system restarts). | |
|
|
|
| |
411 | Critical | (Outdoor Unit) The low pressure switch has | Open low pressure switch error count reached 5 strikes. Check system charge using approach and | |
|
| opened 5 times during one cooling cycle. As a | sub cooling temperatures. Reset by putting outdoor unit control in test mode or resetting low voltage | |
|
| result, the thermostat has shutdown the outdoor | power. | |
|
| unit. |
| |
|
|
|
| |
412 | Moderate | (Outdoor Unit) The outdoor unit pressure is | Unit pressure is above the upper limit. Pressure switch opens at 590 psig (system shuts down) and | |
|
| above the required limit. The system will shut | closes at 418 psig (system restarts). | |
|
| down. |
| |
|
|
|
| |
413 | Critical | (Outdoor Unit) The high pressure switch has | Open high pressure switch error count reached 5 strikes. Check system charge | |
|
| opened 5 times during one cooling cycle. As a | using approach and sub cooling temperatures. Check outdoor fan operation. Check for dirt or debris | |
|
| result, the thermostat has shutdown the outdoor | blocking air flow to outdoor unit. Reset by putting outdoor unit control in test mode or resetting low | |
|
| unit. | voltage power. | |
|
|
|
| |
414 | Critical | (Outdoor Unit) The discharge line temperature | Discharge line temperature is > 279ºF. Make sure coil is clean and airflow unobstructed in and out of | |
|
| is higher than the recommended upper limit of | condenser. Check system operating pressures and compare to unit charging charts in installation | |
|
| 279ºF. | manual. Clears after discharge temperature is < 225ºF. | |
|
|
|
| |
415 | Critical | (Outdoor Unit) The discharge line temperature | Discharge line high temperature error count reached 5 strikes. Make sure coil is clean and airflow | |
|
| has been consistently higher than the recom- | unobstructed in and out of condenser. Check system charge using approach and sub cooling tem- | |
|
| mended upper limit of 279ºF. | peratures. Reset by putting outdoor board in test mode or resetting low voltage power. | |
|
|
|
| |
416 | Critical | (Outdoor Unit) The outdoor coil sensor is either | Sensor being detected open or shorted, or temperature is out of sensor range. | |
|
| open, short−circuited or the temperature is out of | Outdoor unit control will not perform demand or time/temperature defrost operation. (System will still | |
|
| sensor range. As a result the outdoor unit con- | heat or cool.) Clears when outdoor unit control detects proper sensor readings. | |
|
| trol will not perform any defrost tempering. |
| |
|
|
|
| |
417 | Critical | (Outdoor Unit) The outdoor unit sensor is either | Outdoor unit control detects open or shorted sensor, or temperature that is out of sensor range. | |
|
| open, short−circuited or the temperature is out of | Critical Alert after 10 minutes. Reset by replacing sensor. This fault is detected by allowing the unit to | |
|
| sensor range. As a result the outdoor unit con- | run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range | |
|
| trol will not perform any defrost tempering. | after 90 seconds, the board will count one fault. After 5 faults, the board will lock out. Check for | |
|
|
| proper sensor reading and attachment to line. Replace if out−of−specifications. | |
|
|
|
| |
|
|