Lennox International Inc SLP9801, XP2101, XC2105, XC1702, XP1906 Alert Codes and Troubleshooting

Models: CBX40UHV02 EL296V01 CBX32MV06 iComfort Wifi Thermostat SL28003 G71MPP03 SLP9801 XP1702 XP1906 XC1702 XC2105 XP2101

1 72
Download 72 pages 43.71 Kb
Page 53
Image 53

Table 5. Alert Codes and Troubleshooting

Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer

alert button. Minor and Moderate alerts are found only in the Installer alert button.

 

 

 

Alert

 

 

 

Code

Priority

Alert Text

Steps to clear

 

 

 

 

407

Critical

(Outdoor Unit) The required amount of current is

Required amount of current is not passing through Run current transformer. Clears the error after

 

 

not passing through run current transformer.

current is sensed in RUN sensor, or 1 normal compressor run cycle, or after power reset

 

 

 

 

408

Critical

(Outdoor Unit) The compressor is running con-

Compressor runs continuously. Clears the error after 1 normal compressor run

 

 

tinuously.

cycle or after power reset.

 

 

 

 

409

Moderate

(Furnace / Air Handler / Outdoor Unit) The sec-

Secondary voltage is below 18VAC. After 10 minutes, operation is discontinued.

 

 

ondary voltage for the (furnace, air−handler or

Clears the code after voltage is higher than 20 VAC for 2 seconds or after power

 

 

outdoor unit) has fallen below 18VAC. If this

reset.

 

 

continues for 10 minutes, the thermostat will

 

 

 

turn off the (furnace, air−handler or outdoor unit).

 

 

 

 

 

410

Moderate

(Outdoor Unit) The outdoor unit pressure is be-

Unit pressures are below the lower limit. Pressure switch opens at 40 psig (system shuts down) and

 

 

low the required limit.

closes at 90 psig (system restarts).

 

 

 

 

411

Critical

(Outdoor Unit) The low pressure switch has

Open low pressure switch error count reached 5 strikes. Check system charge using approach and

 

 

opened 5 times during one cooling cycle. As a

sub cooling temperatures. Reset by putting outdoor unit control in test mode or resetting low voltage

 

 

result, the thermostat has shutdown the outdoor

power.

 

 

unit.

 

 

 

 

 

412

Moderate

(Outdoor Unit) The outdoor unit pressure is

Unit pressure is above the upper limit. Pressure switch opens at 590 psig (system shuts down) and

 

 

above the required limit. The system will shut

closes at 418 psig (system restarts).

 

 

down.

 

 

 

 

 

413

Critical

(Outdoor Unit) The high pressure switch has

Open high pressure switch error count reached 5 strikes. Check system charge

 

 

opened 5 times during one cooling cycle. As a

using approach and sub cooling temperatures. Check outdoor fan operation. Check for dirt or debris

 

 

result, the thermostat has shutdown the outdoor

blocking air flow to outdoor unit. Reset by putting outdoor unit control in test mode or resetting low

 

 

unit.

voltage power.

 

 

 

 

414

Critical

(Outdoor Unit) The discharge line temperature

Discharge line temperature is > 279ºF. Make sure coil is clean and airflow unobstructed in and out of

 

 

is higher than the recommended upper limit of

condenser. Check system operating pressures and compare to unit charging charts in installation

 

 

279ºF.

manual. Clears after discharge temperature is < 225ºF.

 

 

 

 

415

Critical

(Outdoor Unit) The discharge line temperature

Discharge line high temperature error count reached 5 strikes. Make sure coil is clean and airflow

 

 

has been consistently higher than the recom-

unobstructed in and out of condenser. Check system charge using approach and sub cooling tem-

 

 

mended upper limit of 279ºF.

peratures. Reset by putting outdoor board in test mode or resetting low voltage power.

 

 

 

 

416

Critical

(Outdoor Unit) The outdoor coil sensor is either

Sensor being detected open or shorted, or temperature is out of sensor range.

 

 

open, short−circuited or the temperature is out of

Outdoor unit control will not perform demand or time/temperature defrost operation. (System will still

 

 

sensor range. As a result the outdoor unit con-

heat or cool.) Clears when outdoor unit control detects proper sensor readings.

 

 

trol will not perform any defrost tempering.

 

 

 

 

 

417

Critical

(Outdoor Unit) The outdoor unit sensor is either

Outdoor unit control detects open or shorted sensor, or temperature that is out of sensor range.

 

 

open, short−circuited or the temperature is out of

Critical Alert after 10 minutes. Reset by replacing sensor. This fault is detected by allowing the unit to

 

 

sensor range. As a result the outdoor unit con-

run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range

 

 

trol will not perform any defrost tempering.

after 90 seconds, the board will count one fault. After 5 faults, the board will lock out. Check for

 

 

 

proper sensor reading and attachment to line. Replace if out−of−specifications.

 

 

 

 

 

 

 

table continued on next page

Page 53

icomfort Wi-Fit 7−Day Programmable Communicating Thermostat

Page 53
Image 53
Lennox International Inc SLP9801, XP2101, XC2105, XC1702, XP1906, XP1702, G71MPP03, SL28003 Alert Codes and Troubleshooting

FAQ

What are critical alerts?

Critical alerts are displayed on the Home user screen and indicate urgent issues that need immediate attention.

How can I clear a 407 alert?

To clear a 407 alert, ensure the required amount of current is passing through the run current transformer. If not, follow the steps to clear the error.

What does a 409 alert mean?

A 409 alert indicates that the secondary voltage for the furnace, air handler, or outdoor unit has fallen below the required limit. Follow the steps to clear the code.