Table 5. Alert Codes and Troubleshooting

Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer

alert button. Minor and Moderate alerts are found only in the Installer alert button.

 

 

 

Alert

 

 

 

Code

Priority

Alert Text

Steps to clear

 

 

 

 

418

Moderate

(Outdoor Unit) There is a faulty

Faulty W output circuit.

 

 

cuit.

 

 

 

 

 

419

Critical

(Outdoor Unit) The

W output hardware fault count reached 5 strikes.

 

 

unit has reported more than 5 errors. As a re-

 

 

 

sult, the system has shutdown the outdoor unit.

 

 

 

 

 

420

Critical

(Air Handler) The heat pump defrost cycle has

Defrost cycle lasts longer than 20 minutes. Check heat pump operation. Cleared

 

 

taken more than 20 minutes to complete.

when W1 signal is removed. Applicable only in communicating mode with non−communicating heat

 

 

 

pump.

 

 

 

 

421

Critical

(Outdoor Unit) The

Voltage sensed on W output terminal when Y1 out is deactivated.

 

 

outdoor unit is not wired correctly.

 

 

 

 

 

700

Moderate

(Stat) The temperature sensor in the thermostat

Recalibrate thermostat to clear. Replace thermostat if needed.

 

 

is not working properly.

 

 

 

 

 

701

Moderate

(Stat) The thermostat is reading indoor tempera-

Recalibrate thermostat to clear; cool thermostat; adjust setpoint. Replace thermostat, if needed.

 

 

tures above the pre−programmed limit.

 

 

 

 

 

702

Moderate

(Stat) The thermostat is reading indoor tempera-

Recalibrate thermostat to clear; warm thermostat; adjust setpoint. Replace thermostat, if needed.

 

 

tures below the pre−programmed limit.

 

 

 

 

 

703

Moderate

(Stat) The humidity sensor in the thermostat is

Recalibrate thermostat to clear; adjust setpoint. Replace thermostat, if needed.

 

 

not working properly.

 

 

 

 

 

704

Moderate

(Stat) The thermostat is reading indoor humidity

Recalibrate thermostat to clear. Replace thermostat, if needed.

 

 

levels above the pre−programmed limit.

 

 

 

 

 

705

Moderate

(Stat) The thermostat is reading indoor humidity

Recalibrate thermostat to clear. Replace thermostat, if needed.

 

 

levels below the pre−programmed limit.

 

 

 

 

 

Ohm

 

The ohm reading in the system is either too

Ohm reading between i+ and i− anywhere on the RSBus with supply power off should be between 70

 

and 90 ohms. If above 90 ohms, check and repair wiring, splices or other wiring defects that may be

Check

 

high or too low.

 

causing the excessive resistance. If less than 70 ohms, check for shorted wires.

 

 

 

 

 

 

 

Homeowner Service Alert Codes8

Number

Value

Number

Value

Number

Value

Number

Value

Number

Value

 

 

 

 

 

 

 

 

 

 

3000

Filter 1

3002

Humidifier Pad

3004

Maintenance

4000

User WiFi state change, disable

4002

Image file download failed

 

 

 

 

 

 

 

 

 

 

3001

Filter 2

3003

UV Light

3005

PureAir Maintenance

4001

Firmware download failed

 

 

 

 

 

 

 

 

 

 

 

 

506920−01 09/12

Page 54

Page 54
Image 54
Lennox International Inc G71MPP03, XP2101, XC2105, XC1702 Homeowner Service Alert Codes8, Alert Codes and Troubleshooting