42CallPilot server installation
5Tighten all the nuts that you previously
6Slide the system into the rack.
Check that the inner rail fits together with the outer rail.
7To secure the server in place, install screws in the
For a
—End—
Installing peripheral devices
Perform the following procedure to install the peripheral devices on the CallPilot server.
Step Action
1Optionally, install a perforated shelf for the modem and Tandberg tape drive to sit on.
Nortel recommends that you use a perforated shelf rather than placing the modem and tape drive directly on the CallPilot server equipment. The holes in the perforated shelf promote air flow and cooling.
2Place the modem and tape drive on the perforated shelf or, on an alternative surface.
3Connect one end of the USB cable into the modem. Connect the other end of the USB cable into the rear panel of the server module: USB 2 for the 600r CallPilot server, or USB 1 for the 1005r CallPilot server.
4Connect the analog phone line to the
5Connect one end of the SCSI cable to the tape drive. Connect the other end of the SCSI cable to the SCSI port on the rear panel of the CallPilot server.
Ensure that all connectors are tightened.
Note: You must remove the SCSI terminator before you can connect the tape drive. Ensure that there is a terminator installed on the tape drive.
The 600r hard drive and tape drive are on the same SCSI bus. If a terminator is not installed in the loop, the hard drive may be damaged when the system is powered up.
Nortel CallPilot
Quickstart Guide
5.019 May 2008