Performing preboot checks

Connecting the server to power and starting it 45

6Install and connect the DS30X cable from the switch MGATE card to the CallPilot MPB96, starting from the switch side. The following are guidelines:

The 3 connectors of each DS30X cable going to the MGate card are labeled with DS30X-1 to DS30X-3. Connect the DS30X-1 first, the DS30X-2 second, and the DS30X-3 third. This is important for timing off the MGATE card.

If more then one MPB96 card is installed, first connect the DS30X cable to the topmost MPB96 card, then to the middle card, and then to the bottom card.

Tighten all connectors. Loose connectors can cause loss of service.

Tech tip: It is easier to run the DS30X cable in starting from the telephony switch side. Protect the end connector of the cable.

—End—

Performing preboot checks

Perform the following preboot checks on the CallPilot server to ensure a smooth system boot.

Step Action

1Check that a single-point ground (SPG) is followed for every device requiring power in the CallPilot system. Check that power cords and UPS devices are plugged into SPGs.

2Check that all connectors and cables are properly tightened down and connected where applicable.

3Check that the dongle is plugged into the proper port and the feature key is in it.

—End—

Connecting the server to power and starting it

For 600r servers: when you apply AC power to the 600r server, the server starts automatically. This is part of the BIOS startup sequence. It is important to follow the steps in the order given.

Nortel CallPilot

Quickstart Guide

NN44200-313 01.02 Standard

5.019 May 2008

Copyright © 2007-2008, Nortel Networks

Page 45