Enviro 6G50 76N instruction manual Unconfined Space, Fresh Air Openings For Confined Spaces

Page 12

Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation.

Do not install the water heater in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows.

Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause property damage, serious bodily injury or death.

Unconfined Space

An Unconfined Space is one whose volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces should also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air.

UNUSUALLY TIGHT CONSTRUCTION

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows.

CONFINED SPACE

A Confined Space is one whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space.

Openings must be installed to provide fresh air for combustion, ventilation and dilution in confined spaces. The required size for the openings is dependent on the method used to provide fresh air to the confined space and the total Btu/hr input rating of all appliances installed in the space.

DIRECT VENT APPLIANCES

Appliances installed in a Direct Vent configuration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/hr calculations used to determine the size of openings providing fresh air into confined spaces.

EXHAUST FANS

Where exhaust fans are installed, additional air should be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of fire or explosion may result. It can also create a risk of asphyxiation.

LOUVERS AND GRILLES

The free areas of fresh air openings in instructions that follow do not take in to account presence of louvers, grilles or screens in openings.

The required size of openings for combustion, ventilation and dilution air should be based on the “net free area” of each opening. Where the free area through a design of louver or grille or screen is known, it should be used in calculating the size of opening required to provide the free area specified. Where the louver and grille design and free area are not known, it should be assumed that wood louvers will have 25%

free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles should be fixed in the open position.

Fresh Air Openings For Confined Spaces

The following instructions should be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. Do not refer to these illustrations for the purpose of vent installation. See Installation of Vent System on pages 18-25 for complete venting installation instructions.

Outdoor Air Through Two Openings

FIGURE 6.

The confined space should be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings should communicate directly with the outdoors. See Figure 6.

Each opening should have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening should not be less than 100 square inches (645 cm2).

Outdoor Air Through One Opening

FIGURE 7.

Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, should be provided. See

12

Image 12
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredSafe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Information General Safety Information Table of Contents Qualified Installer or Service Agency Preparing for the InstallationTo Install or Operate the Water Heater IntroductionTypical Installation Replacement Parts and Deliming ProductsRelief Valve Elbow Access Door Condensate Hose and Drain PAN Mixing Valves Less Severe Burns 2nd & 3rd Degree Most Severe BurnsLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsUnconfined Space Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Horizontal Ducts Outdoor AIR Through TWO Vertical DuctsAIR from Other Indoor Spaces Installing the NEW Water Heater Chemical Vapor CorrosionWater Piping Space Heating and Potable Water SystemTemperature-Pressure Relief Valve Thermal ExpansionValve and Pipe Insulation High Altitude Installation Valve Discharge Pipe RequirementsGAS Piping with Flexible Connector GAS Piping with ALL Black Iron Pipe to GAS ControlVent Pipe Assembly Sediment TrapsFilling the Water Heater VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationPlanning the Vent System CondensateBreathing Hazard Carbon Monoxide Gas Blower Assembly Installation Vent Terminal INSTALLATION, SidewallPower Vent Wiring Schematic Figure Vent Termination FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vertical VAA Installations RecommendedInch vent Vertical VAA Installations Inch vent Horizontal VAA InstallationsCould cause illness, asphyxiation and/or even death Page Temperature Regulation Water TemperatureFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Draining and FlushingService To Drain the Water Heater Storage TankTo Flush the Water Heater Storage Tank Leakage Checkpoints Repair Parts List Troubleshooting Guidelines Trouble ShootingLED Status Problem Solution LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Service and Labor Responsibility Claim ProcedureConditions and Exceptions Limitation on Implied WarrantiesGSW Water Heating Hill Street West Fergus, on Canada N1M CHAUFFE-EAU AU GAZ Résidentiel ImpriméINSTALLATION, Utilisation ET Service EN Toute Sécurité ApprobationsDéfinitions Importantes Avertissement Information DE Sécurité Générale AVERTISSEMENT Emplacement DU Nouveau CHAUFFE-EAU Table DES MatièresInstallateur ou organisme de service qualifié Préparation pour l’installationInstallation Type Piècesde Rechange ET Produits DE DétartrageTuyau DE Condensat ET BAC DE Vidange Mélangeurs TableauEmplacement DU Nouveau CHAUFFE-EAU Faits à prendre en considération concernant l’emplacementProtections Thermiques Quantité d’air NécessaireEspaces non clos Espace ClosOuvertures d’air frais pour espaces clos Air extérieur à travers deux ouverturesAIR Externe À Travers Deux Conduits Horizontaux AIR Externe À Travers Deux Conduits VerticauxAIR Provenant D’AUTRES Espaces Intérieurs Installation DU CHAUFFE-EAU Corrosion DE Vapeur ChimiqueConduites d’eau Chauffage DES Locaux ET Systèmes D’EAU PotableExpansion thermique Soupape de décharge à sécurité thermiqueInstallation À Haute Altitude Pressure Relief Valve thermique. discharge outletConduite de gaz Bacs DE SédimentationRemplissage du chauffe-eau Ensemble Tuyau DE VentilationVentilation Terminaison DU Tuyau DE Ventilation Ventilation À AIR PulséPlanification DU Système DE Ventilation CondensatSi un tuyau de ventilation de 2 po est utilisé Si un tuyau de ventilation de 3 po ou 4 po est utiliséInstallation DE L’ENSEMBLE DE LA Soufflante Installation DU Terminal D’ÉVENT, Paroi LatéraleTerminaison DE L’ÉVENT Figure AvertissementSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Installation DU Système DE VENTILATION, Paroi Latérale Installation DU Système DE Ventilation VerticalInstallation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENT Installations verticales de l’EAE RecommandéesÉvent de 3 po Installations horizontales d’EAE Évent de 3 po Installations verticales d’EAEÉvent de 4 po Installations verticales d’EAE Évent de 4 po Installations horizontales d’EAEQUE Faire EN CAS D’ODEUR DE GAZ NE PAS Tenter D’ALLUMER LE Brûleur À LA MainRégulation DE Température Bouton « Cooler » plus froid jusqu’à ce que le réglageConditions DE Mise EN Service Pour Votre InformationConditions Opérationnelles Entretien Périodique Inspection DE LA Tige D’ANODEDdanger Test de soupape de décharge à sécurité thermiqueVidange ET Rinçage Pour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAUPour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Statut DEL Problème Solution Directives DE Dépannagep GEDépannage ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel