methods can increase the rate of anode rod depletion. Once the anode rod is depleted, the tank will start to corrode, eventually developing a leak.

Certain water conditions will cause a reaction between the anode rod and the water. The most common complaint associated with the anode rod is a “rotten egg smell” produced from the presence of hydrogen sulfide gas dissolved in the water. IMPORTANT: Do not remove this rod permanently as it will void any warranties. The parts list includes a special anode rod that can be ordered if water odor or discoloration occurs. NOTE: This rod may reduce but not eliminate water odor problems. The water supply system may require special filtration equipment from a water conditioning company to successfully eliminate all water odor problems.

Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank.

The anode rod should be removed from the water heater tank every 3 years for inspection. NOTE: artificially softened water requires the anode rod to be inspected annually.

The following are typical (but not all) signs of a depleted anode rod: * The majority of the rods diameter is less than 3/8”.

*Significant sections of the support wire (approx. 1/3 or more of the anode rod’s length) are visible.

If the anode rod show signs of either or both it should be replaced.

NOTE: Whether re-installing or replacing the anode rod, check for any leaks and immediately correct if found.

In replacing the anode:

1.Turn off gas supply to the water heater.

2.Shut off the water supply and open a nearby hot water faucet to depressurize the water tank.

3.Drain approximately 5 gallons of water from tank (Refer to “Draining and Flushing” for proper procedures). Close drain valve.

4.Remove old anode rod.

5.Use Teflon® tape or approved pipe sealant on threads and install new anode rod.

6.Turn on water supply and open nearby hot water faucet to purge air from water system. Check for any leaks and immediately correct any if found.

Restart the water heater as directed under “Operating Your Water Heater.” See the Repair Parts Illustration for anode rod location.

It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months.

When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature- Pressure Relief Valve discharge line, and (2) that water discharge will not cause any property damage, as water may be extremely hot. Use care when operating valve as the valve may be hot.

To check the relief valve, lift lever at the end of valve several times, see Figure 29. The valve should seat properly and operate freely.

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining And Flushing on page 30-31. Replace the Temperature-Pressure Relief Valve with a properly rated/sized new one, see Temperature-Pressure Relief Valve on page 15-16 for instructions on replacement.

TEMPERATURE-PRESSURE

RELIEF VALVE

DISCHARGE PIPE

Figure 29.

If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion.

Note: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by “thermal expansion” in a “closed system.” See Closed Water Systems and Thermal Expansion on page 14-15. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.

Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems.

DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH.

Figure 28.

Temperature-Pressure Relief Valve Test

Explosion Hazard

Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code.

Properly sized Temperature-Pressure Relief Valve must be installed in opening provided.

DANGER

Burn hazard.

Hot water discharge.

Keep clear of Temperature- Pressure Relief Valve discharge outlet.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

DRAINING AND FLUSHING

It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures. See Typical Installation section in this manual for location of the water heater components described below.

30

Image 30
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredSafe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Information General Safety Information Table of Contents To Install or Operate the Water Heater Qualified Installer or Service AgencyPreparing for the Installation IntroductionTypical Installation Replacement Parts and Deliming ProductsRelief Valve Elbow Access Door Condensate Hose and Drain PAN Mixing Valves Less Severe Burns 2nd & 3rd Degree Most Severe BurnsLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsFresh Air Openings For Confined Spaces Unconfined SpaceConfined Space Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Horizontal Ducts Outdoor AIR Through TWO Vertical DuctsAIR from Other Indoor Spaces Water Piping Installing the NEW Water HeaterChemical Vapor Corrosion Space Heating and Potable Water SystemTemperature-Pressure Relief Valve Thermal ExpansionValve and Pipe Insulation High Altitude Installation Valve Discharge Pipe RequirementsGAS Piping with Flexible Connector GAS Piping with ALL Black Iron Pipe to GAS ControlFilling the Water Heater Vent Pipe AssemblySediment Traps VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationPlanning the Vent System CondensateBreathing Hazard Carbon Monoxide Gas Blower Assembly Installation Vent Terminal INSTALLATION, SidewallPower Vent Wiring Schematic Figure Vent Termination FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vertical VAA Installations RecommendedInch vent Vertical VAA Installations Inch vent Horizontal VAA InstallationsCould cause illness, asphyxiation and/or even death Page Temperature Regulation Water TemperatureFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Draining and FlushingService To Drain the Water Heater Storage TankTo Flush the Water Heater Storage Tank Leakage Checkpoints Repair Parts List Troubleshooting Guidelines Trouble ShootingLED Status Problem Solution LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Conditions and Exceptions Service and Labor ResponsibilityClaim Procedure Limitation on Implied WarrantiesGSW Water Heating Hill Street West Fergus, on Canada N1M CHAUFFE-EAU AU GAZ Résidentiel ImpriméINSTALLATION, Utilisation ET Service EN Toute Sécurité ApprobationsDéfinitions Importantes Avertissement Information DE Sécurité Générale AVERTISSEMENT Emplacement DU Nouveau CHAUFFE-EAU Table DES MatièresInstallateur ou organisme de service qualifié Préparation pour l’installationInstallation Type Piècesde Rechange ET Produits DE DétartrageTuyau DE Condensat ET BAC DE Vidange Mélangeurs TableauEmplacement DU Nouveau CHAUFFE-EAU Faits à prendre en considération concernant l’emplacementProtections Thermiques Quantité d’air NécessaireOuvertures d’air frais pour espaces clos Espaces non closEspace Clos Air extérieur à travers deux ouverturesAIR Externe À Travers Deux Conduits Horizontaux AIR Externe À Travers Deux Conduits VerticauxAIR Provenant D’AUTRES Espaces Intérieurs Conduites d’eau Installation DU CHAUFFE-EAUCorrosion DE Vapeur Chimique Chauffage DES Locaux ET Systèmes D’EAU PotableExpansion thermique Soupape de décharge à sécurité thermiqueInstallation À Haute Altitude Pressure Relief Valve thermique. discharge outletConduite de gaz Bacs DE SédimentationRemplissage du chauffe-eau Ensemble Tuyau DE VentilationVentilation Terminaison DU Tuyau DE Ventilation Ventilation À AIR PulséSi un tuyau de ventilation de 2 po est utilisé Planification DU Système DE VentilationCondensat Si un tuyau de ventilation de 3 po ou 4 po est utiliséInstallation DE L’ENSEMBLE DE LA Soufflante Installation DU Terminal D’ÉVENT, Paroi LatéraleTerminaison DE L’ÉVENT Figure AvertissementSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Installation DU Système DE VENTILATION, Paroi Latérale Installation DU Système DE Ventilation VerticalInstallation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENT Installations verticales de l’EAE RecommandéesÉvent de 4 po Installations verticales d’EAE Évent de 3 po Installations horizontales d’EAEÉvent de 3 po Installations verticales d’EAE Évent de 4 po Installations horizontales d’EAEQUE Faire EN CAS D’ODEUR DE GAZ NE PAS Tenter D’ALLUMER LE Brûleur À LA MainRégulation DE Température Bouton « Cooler » plus froid jusqu’à ce que le réglageConditions DE Mise EN Service Pour Votre InformationConditions Opérationnelles Entretien Périodique Inspection DE LA Tige D’ANODEDdanger Test de soupape de décharge à sécurité thermiqueVidange ET Rinçage Pour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAUPour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Statut DEL Problème Solution Directives DE Dépannagep GEDépannage ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel