Enviro 6G50 76N instruction manual LED Status Problem Solution

Page 35

#

7

8

9

10

11

12

13

14

15

16

LED STATUS

PROBLEM

 

SOLUTION

 

 

Self diagnostic check has detected

1

Turn the power off for 10-20 seconds then on again to

 

 

 

 

 

clear these error codes.

 

 

 

 

 

a problem with the gas valve driver

 

 

 

 

 

 

 

circuit, internal microprocessor, or

2

If any of these error codes persist or cannot be cleared

 

 

other internal circuits.

 

 

 

- replace the gas control valve/thermostat.

 

 

 

 

 

 

 

1

Turn the power off for 10-20 seconds then on again to

 

 

 

 

 

The gas control valve/thermostat

 

clear these error codes.

 

 

 

 

 

has sensed main burner flame out

 

 

 

 

of proper sequence.

2

Replace the gas control valve/thermostat if this error

 

 

 

 

 

 

code persists.

 

 

Water temperature in the tank has

1

Turn the power off for 10-20 seconds then on again to

 

 

 

clear these error codes.

 

 

exceeded 195° F and has activated

 

 

 

 

 

 

 

the ECO (energy cut off) high

2

Replace the gas control valve/thermostat if the error

 

 

temperature limit.

 

 

 

code persists.

 

 

 

 

 

 

 

1

Press and release both temperature adjust buttons

 

 

Self diagnostic check has detected

 

several times - cycle water heater power off and on.

 

 

 

 

 

that one or both of the temperature

 

 

 

 

adjust buttons are stuck.

2

Replace the gas control valve/thermostat if the error

 

 

 

 

 

 

code persists.

 

 

Self diagnostic check has detected

1

Turn the power off for 10-20 seconds then on again to

 

 

the water temperature sensor

 

clear these error codes.

 

 

 

 

 

(located in the control valve's

 

 

 

 

immersion probe) is either open or

2

Replace the gas control valve/thermostat if the error

 

 

 

 

shorted.

 

code persists.

 

 

 

1

Turn off power to the water heater. Ensure black

 

 

Self diagnostic check has detected

 

resistor wire is not cut, missing, and is installed

 

 

 

between pins 3 & 4 of ignitor assembly plug. Replace

 

 

a problem with black resistor wire

 

 

 

 

ignitor assembly if damaged or defective.

 

 

on the ignitor assembly plug;

 

 

 

 

 

 

 

resistor wire is open or shorted.

2

Replace the gas control valve/thermostat if the error

 

 

 

 

 

 

 

code persists.

 

 

Self diagnostic check has

1

Turn off power to the water heater.

 

 

 

 

 

 

determined resistance of the black

2

Replace the igniter assembly plug.

 

 

resistor wire on ignitor assembly

 

 

 

 

plug is not within tolerance.

3

Replace the gas control valve/thermostat if the error

 

 

 

 

code persists.

 

 

 

1

Ensure air pressure switch hose is not kinked or

 

 

 

 

clogged, ensure the blower housing is clear of any

 

 

 

 

condensation.

 

 

The gas control valve/thermostat

2

Check vent temperature limit switch - if it is determined

 

 

has detected the air pressure switch

 

that the vent temperature limit switch is opening its

 

 

circuit is opening repeatedly during

 

contacts at normal operating temperatures during

 

 

one heating cycle.

 

heating cycle - replace the vent temperature limit

 

 

 

 

switch.

 

 

 

3

Ensure water heater is not over-firing. Call the technical

 

 

 

 

support for further assistance.

 

 

 

 

 

35

Image 35
Contents Whenever maintenance adjustment or service is required Power Vented GAS Models W/HOT Surface IgnitionImportant Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Information General Safety Information Table of Contents Introduction Qualified Installer or Service AgencyPreparing for the Installation To Install or Operate the Water HeaterRelief Valve Elbow Access Door Typical InstallationReplacement Parts and Deliming Products Condensate Hose and Drain PAN Less Severe Burns 2nd & 3rd Degree Most Severe Burns Mixing ValvesFacts to Consider About the Location Locating the NEW Water HeaterAir REQUIREMENTs Insulation BlanketsOutdoor Air Through Two Openings Unconfined SpaceConfined Space Fresh Air Openings For Confined SpacesAIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts Space Heating and Potable Water System Installing the NEW Water HeaterChemical Vapor Corrosion Water PipingValve and Pipe Insulation Temperature-Pressure Relief ValveThermal Expansion Valve Discharge Pipe Requirements High Altitude InstallationGAS Piping with ALL Black Iron Pipe to GAS Control GAS Piping with Flexible ConnectorVenting Vent Pipe AssemblySediment Traps Filling the Water HeaterVent Pipe Termination Termination Clearances Sidewall Power VentBreathing Hazard Carbon Monoxide Gas Planning the Vent SystemCondensate Vent Terminal INSTALLATION, Sidewall Blower Assembly InstallationVent Termination Figure Power Vent Wiring Schematic FigureInstallation of Vertical Vent System Installation of Vent SYSTEM, SidewallVertical VAA Installations Recommended Vent Attenuation Assembly InstallationCould cause illness, asphyxiation and/or even death Inch vent Vertical VAA InstallationsInch vent Horizontal VAA Installations Page Water Temperature Temperature RegulationOperational Conditions For Your InformationStart UP Conditions Anode ROD Inspection Periodic MaintenanceDraining and Flushing Temperature-Pressure Relief Valve TestTo Flush the Water Heater Storage Tank ServiceTo Drain the Water Heater Storage Tank Leakage Checkpoints Repair Parts List LED Status Problem Solution Troubleshooting GuidelinesTrouble Shooting LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Limitation on Implied Warranties Service and Labor ResponsibilityClaim Procedure Conditions and ExceptionsGSW Water Heating Hill Street West Fergus, on Canada N1M Imprimé CHAUFFE-EAU AU GAZ RésidentielDéfinitions Importantes INSTALLATION, Utilisation ET Service EN Toute SécuritéApprobations Information DE Sécurité Générale Avertissement AVERTISSEMENT Table DES Matières Emplacement DU Nouveau CHAUFFE-EAUPréparation pour l’installation Installateur ou organisme de service qualifiéPiècesde Rechange ET Produits DE Détartrage Installation TypeTuyau DE Condensat ET BAC DE Vidange Tableau MélangeursFaits à prendre en considération concernant l’emplacement Emplacement DU Nouveau CHAUFFE-EAUQuantité d’air Nécessaire Protections ThermiquesAir extérieur à travers deux ouvertures Espaces non closEspace Clos Ouvertures d’air frais pour espaces closAIR Provenant D’AUTRES Espaces Intérieurs AIR Externe À Travers Deux Conduits HorizontauxAIR Externe À Travers Deux Conduits Verticaux Chauffage DES Locaux ET Systèmes D’EAU Potable Installation DU CHAUFFE-EAUCorrosion DE Vapeur Chimique Conduites d’eauSoupape de décharge à sécurité thermique Expansion thermiquePressure Relief Valve thermique. discharge outlet Installation À Haute AltitudeBacs DE Sédimentation Conduite de gazVentilation Remplissage du chauffe-eauEnsemble Tuyau DE Ventilation Ventilation À AIR Pulsé Terminaison DU Tuyau DE VentilationSi un tuyau de ventilation de 3 po ou 4 po est utilisé Planification DU Système DE VentilationCondensat Si un tuyau de ventilation de 2 po est utiliséInstallation DU Terminal D’ÉVENT, Paroi Latérale Installation DE L’ENSEMBLE DE LA SoufflanteSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Terminaison DE L’ÉVENT FigureAvertissement Installation DU Système DE Ventilation Vertical Installation DU Système DE VENTILATION, Paroi LatéraleInstallations verticales de l’EAE Recommandées Installation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENTÉvent de 4 po Installations horizontales d’EAE Évent de 3 po Installations horizontales d’EAEÉvent de 3 po Installations verticales d’EAE Évent de 4 po Installations verticales d’EAENE PAS Tenter D’ALLUMER LE Brûleur À LA Main QUE Faire EN CAS D’ODEUR DE GAZBouton « Cooler » plus froid jusqu’à ce que le réglage Régulation DE TempératureConditions Opérationnelles Conditions DE Mise EN ServicePour Votre Information Inspection DE LA Tige D’ANODE Entretien PériodiqueTest de soupape de décharge à sécurité thermique DdangerPour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Vidange ET RinçagePour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Dépannage Statut DEL Problème SolutionDirectives DE Dépannagep GE ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel