Enviro 6G50 76N Vent Attenuation Assembly Installation, Vertical VAA Installations Recommended

Page 24

VENT ATTENUATION ASSEMBLY

INSTALLATION INSTRUCTIONS

The Vent Attenuation Assembly (VAA) is designed to provide a reduction in fan noise created in the blower wheel. This installation of this VAA is optional. Review directions thoroughly prior to installing the new VAA. Please contact the manufacturer of the water heater as shown in the instruction manual with any questions or for additional product support.

VENT ATTENUATION ASSEMBLY KIT PARTS LIST

The kit consists of the following items. If a part is missing, use the contact information in the instruction manual to acquire missing component(s).

vent attenuation assembly

flexible tubing

hose barb

hex plug (installed on VAA)

instruction sheet

VENT ATTENUATION ASSEMBLY INSTALLATION

The VAA is designed for both vertical and horizontal installations. The vertical installation does not require the additional hose barb and flexible tubing. However, the horizontal installation will require the hose barb and flexible tubing to release condensate buildup from the VAA. See instructions and diagrams that follow for a more detailed description.

supplied with kit) that may be found at a local hardware store. Failure to properly support the VAA and the surrounding vent pipe could create a hazardous situation. DO NOT puncture any surface of the VAA.

5.Confirm that the hex plug is securely installed in the 1/2” fitting found on the center of the VAA pipe. It is imperative that the plug is secure and air tight to prevent any combustion gases escaping into the room. If the plug is not securely tightened, remove and reinstall using Teflon tape on the threads. Since neither hose barb nor flexible tubing is used on the VAA, any unused open barb fittings on vent pipe assembly #2 need to be plugged using break-away plugs. Once installed along with the rest of the vent configuration, make sure to operate the unit through at least one heat up cycle to ensure there is no leakage around the plug or any joints of the VAA or vent pipe system.

Breathing Hazard - Carbon Monoxide Gas

Do NOT block the holes in the hex plug of vent pipe assembly #1.

Do NOT elevate any portion of the field supplied drain line beyond the 1/2" adaptor above the adaptor. This

must be true for entire length of the drain line including the exit into an appropriate drain.

Condensate lines must be free and clear of debris and must not allow back flow through drain line. Condensate lines must be able to flow freely to an appropriate drain.

Do not allow condensate lines to become crimped closed.

Analyze entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Vertical VAA Installations (Recommended)

1.The VAA is designed to accept two inch PVC pipe into the adapters on both ends. The VAA can be installed to the piping from either side (there is no specific inlet or outlet). For optimum performance, install VAA as close as possible to the blower assembly.

2.Following the vent pipe manufacturer ’s instruction, glue the two inch PVC pipe coming from the blower into the VAA.

3.Perform the same sequence on the PVC pipe coming from the exhaust side (vent terminal side) of the VAA.

4.Make sure the VAA and vent pipe is supported securely to a permanent fixture (stud or wall). Use standard support straps (not

FIGURE 22: Typical Vertical Installation

Horizontal VAA Installations

1.The VAA is designed to accept two inch PVC pipe into the adapters on both ends. The VAA can be installed to the piping from either side (there is no specific inlet or outlet). For optimum performance, install VAA as close as possible to the blower assembly.

2.Following the vent pipe manufacturer’s instruction, glue the two inch PVC pipe coming from the blower into the VAA. Make sure the 1/2” fitting is on the bottom side of the VAA. This will be used to run the condensate hose to a suitable drain. See typical vent installation in Figure 23.

3.Perform the same sequence on the PVC pipe coming from the exhaust side (vent terminal side) of the VAA.

4.Make sure the VAA and vent pipe is supported securely to a permanent fixture (stud or wall). Use standard support straps (not supplied with kit) that may be found at a local hardware store. Failure to properly support the VAA and the surrounding vent pipe could create a hazardous situation. DO NOT puncture any surface of the VAA.

5.Remove hex plug from the center pipe of the VAA. Locate the hose barb and install into the 1/2” fitting on the center of the VAA. Using Teflon tape on the threads, install hose barb into 1/2” fitting securely. It is imperative that the hose barb is secure and tight to prevent any combustion gases escaping into the room.

6.Locate flexible tubing. Slide one end of tube over the hose barb located on the center pipe of the VAA. The ridges on the hose barb should prevent the tube from sliding off, however, to ensure there are no leaks and possible dislocation from hose barb, use a wire tie or hose clamp (not supplied with kit) and secure.

24

Image 24
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredSafe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Information General Safety Information Table of Contents Qualified Installer or Service Agency Preparing for the InstallationTo Install or Operate the Water Heater IntroductionTypical Installation Replacement Parts and Deliming ProductsRelief Valve Elbow Access Door Condensate Hose and Drain PAN Mixing Valves Less Severe Burns 2nd & 3rd Degree Most Severe BurnsLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsUnconfined Space Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Horizontal Ducts Outdoor AIR Through TWO Vertical DuctsAIR from Other Indoor Spaces Installing the NEW Water Heater Chemical Vapor CorrosionWater Piping Space Heating and Potable Water SystemTemperature-Pressure Relief Valve Thermal ExpansionValve and Pipe Insulation High Altitude Installation Valve Discharge Pipe RequirementsGAS Piping with Flexible Connector GAS Piping with ALL Black Iron Pipe to GAS ControlVent Pipe Assembly Sediment TrapsFilling the Water Heater VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationPlanning the Vent System CondensateBreathing Hazard Carbon Monoxide Gas Blower Assembly Installation Vent Terminal INSTALLATION, SidewallPower Vent Wiring Schematic Figure Vent Termination FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vertical VAA Installations RecommendedInch vent Vertical VAA Installations Inch vent Horizontal VAA InstallationsCould cause illness, asphyxiation and/or even death Page Temperature Regulation Water TemperatureFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Draining and FlushingService To Drain the Water Heater Storage TankTo Flush the Water Heater Storage Tank Leakage Checkpoints Repair Parts List Troubleshooting Guidelines Trouble ShootingLED Status Problem Solution LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Service and Labor Responsibility Claim ProcedureConditions and Exceptions Limitation on Implied WarrantiesGSW Water Heating Hill Street West Fergus, on Canada N1M CHAUFFE-EAU AU GAZ Résidentiel ImpriméINSTALLATION, Utilisation ET Service EN Toute Sécurité ApprobationsDéfinitions Importantes Avertissement Information DE Sécurité Générale AVERTISSEMENT Emplacement DU Nouveau CHAUFFE-EAU Table DES MatièresInstallateur ou organisme de service qualifié Préparation pour l’installationInstallation Type Piècesde Rechange ET Produits DE DétartrageTuyau DE Condensat ET BAC DE Vidange Mélangeurs TableauEmplacement DU Nouveau CHAUFFE-EAU Faits à prendre en considération concernant l’emplacementProtections Thermiques Quantité d’air NécessaireEspaces non clos Espace ClosOuvertures d’air frais pour espaces clos Air extérieur à travers deux ouverturesAIR Externe À Travers Deux Conduits Horizontaux AIR Externe À Travers Deux Conduits VerticauxAIR Provenant D’AUTRES Espaces Intérieurs Installation DU CHAUFFE-EAU Corrosion DE Vapeur ChimiqueConduites d’eau Chauffage DES Locaux ET Systèmes D’EAU PotableExpansion thermique Soupape de décharge à sécurité thermiqueInstallation À Haute Altitude Pressure Relief Valve thermique. discharge outletConduite de gaz Bacs DE SédimentationRemplissage du chauffe-eau Ensemble Tuyau DE VentilationVentilation Terminaison DU Tuyau DE Ventilation Ventilation À AIR PulséPlanification DU Système DE Ventilation CondensatSi un tuyau de ventilation de 2 po est utilisé Si un tuyau de ventilation de 3 po ou 4 po est utiliséInstallation DE L’ENSEMBLE DE LA Soufflante Installation DU Terminal D’ÉVENT, Paroi LatéraleTerminaison DE L’ÉVENT Figure AvertissementSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Installation DU Système DE VENTILATION, Paroi Latérale Installation DU Système DE Ventilation VerticalInstallation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENT Installations verticales de l’EAE RecommandéesÉvent de 3 po Installations horizontales d’EAE Évent de 3 po Installations verticales d’EAEÉvent de 4 po Installations verticales d’EAE Évent de 4 po Installations horizontales d’EAEQUE Faire EN CAS D’ODEUR DE GAZ NE PAS Tenter D’ALLUMER LE Brûleur À LA MainRégulation DE Température Bouton « Cooler » plus froid jusqu’à ce que le réglageConditions DE Mise EN Service Pour Votre InformationConditions Opérationnelles Entretien Périodique Inspection DE LA Tige D’ANODEDdanger Test de soupape de décharge à sécurité thermiqueVidange ET Rinçage Pour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAUPour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Statut DEL Problème Solution Directives DE Dépannagep GEDépannage ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel