INSTALLING THE NEW WATER HEATER

CHEMICAL VAPOR CORROSION

CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.

Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive.

Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).

Water Piping

This water heater should not be connected to any heating systems or component(s) used with a non-potable water heating appliance.

All piping components connected to this unit for space heating applications should be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment should not be introduced into this system.

When the system requires water for space heating at temperatures higher than required for domestic water purposes, a mixing valve must be installed. Please refer to Figure 2 for suggested piping arrangement.

SPACE HEATING AND POTABLE WATER SYSTEM

This appliance has been design certified as complying with American National Standard/CSA Standard for water heaters and is considered suitable for Water (Potable) Heating and Space Heating.

DANGER

Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.

Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.

Feel water before bathing or showering.

Temperature limiting valves are available.

Read instruction manual for safe temperature setting.

Your water heater is equipped with inlet/outlet connections for use in space heating applications (see Figure 2). If this water heater is to be used to supply both space heating and potable (drinking) water, the instructions listed below must be followed:

• Be sure to follow the manual(s) shipped with the air handler or other

type heating system.

• This water heater is not to be used as a replacement for an existing

boiler installation.

• Do not use with piping that has been treated with chromates, boiler

seal or other chemicals and do not add any chemicals to the water

heater piping

• If the space heating system requires water temperatures in excess of

120°F (49°C), a mixing valve must be installed per the manufacturer’s

HOTTER WATER CAN SCALD:

Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/mentally handicapped. If anyone using hot water fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using lowest possible temperature setting that satisfies your hot water needs, a means such as a mixing valve, should be used at hot water taps used by these people or at the water heater, see Figure 2. Valves for reducing point of use temperature by mixing cold and hot water are also available:

Consult a Qualified Installer or Service Agency. Follow manufacturer’s instructions for installation of valves. Before changing the factory setting on thermostat, read “Temperature Regulation” section in this manual.

instructions in the potable hot water supply to limit the risk of scald

injury.

• Pumps, valves, piping and fi ttings must be compatible with potable

water.

• A properly installed flow control valve is required to prevent

thermosiphoning. Thermosiphoning is the result of a continuous

flow of water through the air handler circuit during the off cycle.

Weeping (blow off) of the temperature and pressure relief valve

(T & P) or higher than normal water temperatures are the first signs

of thermosiphoning.

• The hot water line from the water heater should be vertical past

any mixing valve or supply line to the heating system to remove air

bubbles from the system.

• Do not connect the water heater to any system or components

previously used with non-potable water heating appliances when

used to supply potable water.

Closed Water Systems

Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system to be a closed system.

14

Image 14
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredImportant Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Information General Safety Information Table of Contents To Install or Operate the Water Heater Qualified Installer or Service AgencyPreparing for the Installation IntroductionRelief Valve Elbow Access Door Typical InstallationReplacement Parts and Deliming Products Condensate Hose and Drain PAN Mixing Valves Less Severe Burns 2nd & 3rd Degree Most Severe BurnsLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsFresh Air Openings For Confined Spaces Unconfined SpaceConfined Space Outdoor Air Through Two OpeningsAIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts Water Piping Installing the NEW Water HeaterChemical Vapor Corrosion Space Heating and Potable Water SystemValve and Pipe Insulation Temperature-Pressure Relief ValveThermal Expansion High Altitude Installation Valve Discharge Pipe RequirementsGAS Piping with Flexible Connector GAS Piping with ALL Black Iron Pipe to GAS ControlFilling the Water Heater Vent Pipe AssemblySediment Traps VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationBreathing Hazard Carbon Monoxide Gas Planning the Vent SystemCondensate Blower Assembly Installation Vent Terminal INSTALLATION, SidewallPower Vent Wiring Schematic Figure Vent Termination FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vertical VAA Installations RecommendedCould cause illness, asphyxiation and/or even death Inch vent Vertical VAA InstallationsInch vent Horizontal VAA Installations Page Temperature Regulation Water TemperatureOperational Conditions For Your InformationStart UP Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Draining and FlushingTo Flush the Water Heater Storage Tank ServiceTo Drain the Water Heater Storage Tank Leakage Checkpoints Repair Parts List LED Status Problem Solution Troubleshooting GuidelinesTrouble Shooting LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Conditions and Exceptions Service and Labor ResponsibilityClaim Procedure Limitation on Implied WarrantiesGSW Water Heating Hill Street West Fergus, on Canada N1M CHAUFFE-EAU AU GAZ Résidentiel ImpriméDéfinitions Importantes INSTALLATION, Utilisation ET Service EN Toute SécuritéApprobations Avertissement Information DE Sécurité Générale AVERTISSEMENT Emplacement DU Nouveau CHAUFFE-EAU Table DES MatièresInstallateur ou organisme de service qualifié Préparation pour l’installationInstallation Type Piècesde Rechange ET Produits DE DétartrageTuyau DE Condensat ET BAC DE Vidange Mélangeurs TableauEmplacement DU Nouveau CHAUFFE-EAU Faits à prendre en considération concernant l’emplacementProtections Thermiques Quantité d’air NécessaireOuvertures d’air frais pour espaces clos Espaces non closEspace Clos Air extérieur à travers deux ouverturesAIR Provenant D’AUTRES Espaces Intérieurs AIR Externe À Travers Deux Conduits HorizontauxAIR Externe À Travers Deux Conduits Verticaux Conduites d’eau Installation DU CHAUFFE-EAUCorrosion DE Vapeur Chimique Chauffage DES Locaux ET Systèmes D’EAU PotableExpansion thermique Soupape de décharge à sécurité thermiqueInstallation À Haute Altitude Pressure Relief Valve thermique. discharge outletConduite de gaz Bacs DE SédimentationVentilation Remplissage du chauffe-eauEnsemble Tuyau DE Ventilation Terminaison DU Tuyau DE Ventilation Ventilation À AIR PulséSi un tuyau de ventilation de 2 po est utilisé Planification DU Système DE VentilationCondensat Si un tuyau de ventilation de 3 po ou 4 po est utiliséInstallation DE L’ENSEMBLE DE LA Soufflante Installation DU Terminal D’ÉVENT, Paroi LatéraleSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Terminaison DE L’ÉVENT FigureAvertissement Installation DU Système DE VENTILATION, Paroi Latérale Installation DU Système DE Ventilation VerticalInstallation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENT Installations verticales de l’EAE RecommandéesÉvent de 4 po Installations verticales d’EAE Évent de 3 po Installations horizontales d’EAEÉvent de 3 po Installations verticales d’EAE Évent de 4 po Installations horizontales d’EAEQUE Faire EN CAS D’ODEUR DE GAZ NE PAS Tenter D’ALLUMER LE Brûleur À LA MainRégulation DE Température Bouton « Cooler » plus froid jusqu’à ce que le réglageConditions Opérationnelles Conditions DE Mise EN ServicePour Votre Information Entretien Périodique Inspection DE LA Tige D’ANODEDdanger Test de soupape de décharge à sécurité thermiquePour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Vidange ET RinçagePour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Dépannage Statut DEL Problème SolutionDirectives DE Dépannagep GE ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel