Enviro 6G50 76N instruction manual GAS Piping with Flexible Connector

Page 17

Failure to replace standard orifice with a high altitude orifice when installed above 10,100 feet (3,079 m) could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact your gas supplier for any specific changes which may be required in your area.

Gas Piping

Fire and Explosion Hazard

Do not use water heater with any gas other than the gas shown on the rating plate.

Excessive pressure to gas control valve can cause serious injury or death

Turn off gas lines during installation.

Contact qualified installer or service agency.

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input.

All gas piping must comply with local codes and ordinances or with the Natural Gas and Propane Installation Code (CAN/CSA B149.1). Copper or brass tubing and fittings (except tin lined copper tubing) should not be used.

If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also turn “off” the gas at each appliance. Leave all gas appliances shut “off” until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of the Natural Gas and Propane Installation Code (CAN/CSA B149.1) and your gas supplier concerning pipe size.

There must be:

A readily accessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases.

The appliance and its gas connection must be leak tested before placing the appliance in operation.

The appliance and its individual Shut-off valve should be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It should be isolated from the gas supply piping system by closing its individual manual Shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13.

FIGURE 12. GAS PIPING WITH

FLEXIBLE CONNECTOR.

FIGURE 13. GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

17

Image 17
Contents Whenever maintenance adjustment or service is required Power Vented GAS Models W/HOT Surface IgnitionImportant Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Information General Safety Information Table of Contents Preparing for the Installation Qualified Installer or Service AgencyTo Install or Operate the Water Heater IntroductionRelief Valve Elbow Access Door Typical InstallationReplacement Parts and Deliming Products Condensate Hose and Drain PAN Less Severe Burns 2nd & 3rd Degree Most Severe Burns Mixing ValvesFacts to Consider About the Location Locating the NEW Water HeaterAir REQUIREMENTs Insulation BlanketsConfined Space Unconfined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsAIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts Chemical Vapor Corrosion Installing the NEW Water HeaterWater Piping Space Heating and Potable Water SystemValve and Pipe Insulation Temperature-Pressure Relief ValveThermal Expansion Valve Discharge Pipe Requirements High Altitude InstallationGAS Piping with ALL Black Iron Pipe to GAS Control GAS Piping with Flexible ConnectorSediment Traps Vent Pipe AssemblyFilling the Water Heater VentingVent Pipe Termination Termination Clearances Sidewall Power VentBreathing Hazard Carbon Monoxide Gas Planning the Vent SystemCondensate Vent Terminal INSTALLATION, Sidewall Blower Assembly InstallationVent Termination Figure Power Vent Wiring Schematic FigureInstallation of Vertical Vent System Installation of Vent SYSTEM, SidewallVertical VAA Installations Recommended Vent Attenuation Assembly InstallationCould cause illness, asphyxiation and/or even death Inch vent Vertical VAA InstallationsInch vent Horizontal VAA Installations Page Water Temperature Temperature RegulationOperational Conditions For Your InformationStart UP Conditions Anode ROD Inspection Periodic MaintenanceDraining and Flushing Temperature-Pressure Relief Valve TestTo Flush the Water Heater Storage Tank ServiceTo Drain the Water Heater Storage Tank Leakage Checkpoints Repair Parts List LED Status Problem Solution Troubleshooting GuidelinesTrouble Shooting LED Status Problem Solution Troubleshooting Guidelines Troubleshootinotesg Guidelines Troubleshootinotesg Guidelines Claim Procedure Service and Labor ResponsibilityConditions and Exceptions Limitation on Implied WarrantiesGSW Water Heating Hill Street West Fergus, on Canada N1M Imprimé CHAUFFE-EAU AU GAZ RésidentielDéfinitions Importantes INSTALLATION, Utilisation ET Service EN Toute SécuritéApprobations Information DE Sécurité Générale Avertissement AVERTISSEMENT Table DES Matières Emplacement DU Nouveau CHAUFFE-EAUPréparation pour l’installation Installateur ou organisme de service qualifiéPiècesde Rechange ET Produits DE Détartrage Installation TypeTuyau DE Condensat ET BAC DE Vidange Tableau MélangeursFaits à prendre en considération concernant l’emplacement Emplacement DU Nouveau CHAUFFE-EAUQuantité d’air Nécessaire Protections ThermiquesEspace Clos Espaces non closOuvertures d’air frais pour espaces clos Air extérieur à travers deux ouverturesAIR Provenant D’AUTRES Espaces Intérieurs AIR Externe À Travers Deux Conduits HorizontauxAIR Externe À Travers Deux Conduits Verticaux Corrosion DE Vapeur Chimique Installation DU CHAUFFE-EAUConduites d’eau Chauffage DES Locaux ET Systèmes D’EAU PotableSoupape de décharge à sécurité thermique Expansion thermiquePressure Relief Valve thermique. discharge outlet Installation À Haute AltitudeBacs DE Sédimentation Conduite de gazVentilation Remplissage du chauffe-eauEnsemble Tuyau DE Ventilation Ventilation À AIR Pulsé Terminaison DU Tuyau DE VentilationCondensat Planification DU Système DE VentilationSi un tuyau de ventilation de 2 po est utilisé Si un tuyau de ventilation de 3 po ou 4 po est utiliséInstallation DU Terminal D’ÉVENT, Paroi Latérale Installation DE L’ENSEMBLE DE LA SoufflanteSchéma DU Câblage DE L’ÉVENT À AIR Propulsé Figure Terminaison DE L’ÉVENT FigureAvertissement Installation DU Système DE Ventilation Vertical Installation DU Système DE VENTILATION, Paroi LatéraleInstallations verticales de l’EAE Recommandées Installation DE L’ENSEMBLE D’ATTÉNUATION DE L’ÉVENTÉvent de 3 po Installations verticales d’EAE Évent de 3 po Installations horizontales d’EAEÉvent de 4 po Installations verticales d’EAE Évent de 4 po Installations horizontales d’EAENE PAS Tenter D’ALLUMER LE Brûleur À LA Main QUE Faire EN CAS D’ODEUR DE GAZBouton « Cooler » plus froid jusqu’à ce que le réglage Régulation DE TempératureConditions Opérationnelles Conditions DE Mise EN ServicePour Votre Information Inspection DE LA Tige D’ANODE Entretien PériodiqueTest de soupape de décharge à sécurité thermique DdangerPour Rincer LE Réservoir DE Stockage DU CHAUFFE-EAU Vidange ET RinçagePour Vidanger LE Réservoir DE Stockage DU CHAUFFE- EAU Points DE Vérification DES Fuites Liste DE Pièces DE Rechange Dépannage Statut DEL Problème SolutionDirectives DE Dépannagep GE ’assurer que le capteur de flamme établit un bon contact Problème Cause Solution Directivesmarquesde Dépannage Directivesmarquesde Dépannage Garantie Limitée Pour GAZ Résidentiel