Agilent Technologies n3305a, n3304a, n3301a, n3303a, n3306a manual Transition Time Slew Rate Examples

Models: n3303a n3304a n3300a n3302a n3306a n3301a n3305a

1 102
Download 102 pages 27.56 Kb
Page 28
Image 28

General Information - 2

Therefore, both minimum transition time and slew rate must be considered when determining the actual transition time. This is shown in Figure 2-8, which shows the minimum transition time for a given slew rate as a horizontal line, and at about a 13.3% or greater load change, the slew rate increases from the minimum transition time to the Maximum transition time at a 100% load change. The actual transition time will be either the minimum transition time, or the total slew time (transition divided by slew rate), whichever is longer.

Use the following formula to calculate the minimum transition time (MinTT) for a given slew rate:

MinTT (in seconds) =

__________8__________

slew rate (in amps/second)

 

Use the following formula to calculate the maximum transition time (MaxTT) for a given slew rate:

MaxTT (in seconds) =

__________60__________

slew rate (in amps/second)

 

NOTE: In voltage mode, all minimum transition times are based on a low-capacitance current source. These transition times are affected by capacitive loading of the inputs. For example, a capacitance of 2.2 microfarads increases the 85 microsecond minimum transition time (shown in the table) to 110 microseconds.

Minimum

 

 

 

 

 

 

 

 

 

 

Maximum

Minimum

Transition

 

 

 

 

 

 

 

 

 

 

60000

Transition

 

Time

 

 

 

 

Rate

 

 

s

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lew

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

est

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

8000s

 

 

 

 

 

 

 

 

 

 

 

 

 

8000s

 

 

 

 

 

 

 

 

 

 

 

 

6000s

 

 

 

 

 

 

 

e

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lew

Rat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

Time

800s

 

 

 

 

 

 

 

 

 

 

600s

 

Time

800s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rate

B

 

 

 

 

 

 

 

 

 

 

Slew

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80s

 

 

 

 

 

 

 

 

 

 

 

 

 

85s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60s

 

 

 

 

 

 

 

 

e

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lew

Rat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

s

16s

 

 

 

 

 

 

 

 

 

 

 

 

te

 

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

12s

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5%

13.3%

16.7%

 

50%

 

100%

 

 

 

 

Current (% of full scale)

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

Rate

 

60000s

 

 

 

 

lew

 

 

 

 

 

 

 

 

 

 

 

 

est

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w

 

 

 

 

 

 

 

 

lo

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000s

 

 

 

 

e

A

 

 

 

 

 

 

 

 

 

 

 

 

lew

Rat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600s

 

 

 

 

Rate

B

 

 

 

 

Slew

 

 

 

 

 

 

 

astest

 

 

 

 

 

 

 

120s

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

5%

13.3%

16.7%

 

50%

100%

 

Voltage (% of full scale)

A.B.

Figure 2-8. Transition Time Slew Rate Examples

29

Page 28
Image 28
Agilent Technologies n3305a, n3304a, n3301a, n3303a, n3306a, n3302a, n3300a manual Transition Time Slew Rate Examples