Wiring guidelines
Touch Panels require regulated 12 VDC power to operate properly. The AXCESS Central Controller supplies power via the AXlink cable. The maximum wiring distance between the control system and Touch Panel is determined by power consumption, supplied voltage, and the wire gauge used for the cable. Figure 13 lists wire sizes and the maximum lengths allowable between the Touch Panel and control system. The maximum wiring lengths for using AXlink power are based on a minimum of 13.5 volts available at the control system’s power supply.
Figure13
Wiring guidelines 800 mA. See the Specifications section for power information.
Note
For information on the maxi- mum power consumption of each device, see the Specifications section.
Wiring guidelines for Touch Panel (800
Wire size | Maximum wiring length |
|
|
18 AWG | 146.71 feet (44.71 m) |
20 AWG | 92.8 feet (28.29 m) |
22 AWG | 57.9 feet (17.65 m) |
24 AWG | 34.5 feet (10.52 m) |
If you install the Touch Panel farther away from the control system than recommended in Figure 13, connect an external 12 VDC power supply as shown in the wiring diagrams in this section.