Designing An Isolated Foundation

If the genset cannot be mounted directly on a floor slab, or if it is desirable to isolate it from the floor slab, then a separate foundation slab must be designed.

A massive concrete foundation is not required. Outside dimensions of the foundation should exceed the outside genset dimensions by 12in (300mm).

For single genset installation, the foundation weight should be a minimum of 1.50 times the genset wet weight.

For multiple genset installation, the foundation weight should be a minimum of 2.0 times the genset wet weight.

Figure 2‐3 shows a method to calculate foundation thickness and the soil bearing load of the foundation and generator set. The soil load bearing capacity under the foundation must equal or exceed the load from the foundation and genset. If it does not, then a footing, as shown in Figure 2‐4 must be added to spread the load over a larger area.

Figure 2‐3 Calculate Soil Bearing Load (SBL) Capacity

Figure 2‐4 Typical Footing on Foundation in Soil With Low Soil Load Bearing Capacity

MN2408

General Information 2‐7

Page 17
Image 17
Baldor GLC30, GLC60, GLC105, GLC45, GLC20 Designing An Isolated Foundation, ‐3 Calculate Soil Bearing Load SBL Capacity