Baldor GLC60, GLC10, GLC45 Battery Charger, Battery Cables, ‐10 Typical Battery Cable Calculations

Models: GLC40 GLC25 GLC15 GLC100 GLC30 GLC65 GLC20 GLC45 GLC105 GLC60 GLC10

1 114
Download 114 pages 7.44 Kb
Page 23
Image 23

Battery Charger

An engine mounted alternator charges the batteries during engine operation. Standby gensets should include a solid state battery charger that is connected to utility power so the battery is charged continuously while the genset is not running. The battery charger should be connected to the utility power emergency circuit. The batteries on prime power gensets are charged by the engine mounted alternator, if equipped.

The output of the battery charger or the belt driven alternator must be connected directly to the battery or to the battery terminals on the starter to prevent the electronic governor from acting erratically. Make control connections to the genset control using a conduit with a flexible section at the genset to avoid damage due to genset vibrations.

Battery Cables

The wire size (wire gauge) of the cables connecting the starter to the batteries must be large enough to ensure proper voltage at the engine starter motor during cranking. The total cranking circuit resistance includes the resistance of the cables from the starting motor to the battery and the resistance of all relays, solenoids, switches, and connections. The resistance of various sizes of cables is shown in Figure 2‐10. For purposes of calculating cranking circuit resistance to select cable size, the resistance of each connection can be taken as .00001 ohms and the resistance of each relay, solenoid, and switch can be taken as .0002 ohms. Figure 2‐10 illustrates an example of a typical cranking circuit resistance calculation.

Figure 2‐10 Typical Battery Cable Calculations

MN2408

General Information 2‐13