Alarms

Following alarms are available:

Sensor fail (FLS) see Table 4‐10

 

Sensor fail is detected when measured value is 6% out of selected sensor characteristic.

 

Sensor fail is indicated by ##### symbol instead measured value.

Warning (WRN) see Table 4‐10

 

When warning comes up, only alarm outputs and common warning output are closed.

Shut down (SD) see Table 4‐10

 

When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL

 

SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and

 

common shutdown output are closed. Active or not reset protection disables start.

 

Table 4‐10 Possible Warnings

Events specification

 

Protection type

 

Wrn Oil press

 

WRN

 

Sd Oil press

 

SD

 

Wrn Water temp

 

WRN

 

Sd Water temp

 

SD

 

Wrn Wtemp Low

 

WRN

 

Wrn Fuel Level

 

WRN

 

Sd Fuel Level

 

SD

 

Battery voltage <, >

 

WRN

 

Battery flat

 

SD

 

Start fail

 

SD

 

Vgen <, >

 

SD

 

Vgen unbl

 

SD

 

Fgen <, >

 

SD

 

Igen unbl

 

SD

 

Overload

 

SD

 

RPM over

 

SD

 

RPM under

 

SD

 

PickupFault

 

SD

 

Stop fail

 

SD

 

WrnServiceTime

 

WRN

 

Emergency Stop

 

SD

 

ECU Common Warning

 

WRN

 

ECU Shutdown

 

SD

 

4‐4 Operation

MN2408

Page 44
Image 44
Baldor GLC60, GLC105, GLC45, GLC20, GLC65 Alarms, Sensor fail FLS see ‐10, Shut down SD see ‐10, ‐10 Possible Warnings